  "version": 2,
  "polls": [
    {
      "name": "ZSW1 + actual (40110-40111)",
      "fc": 3,
      "addr": 109,
      "qty": 2,
      "slaveId": 1,
      "interval": 1000,
      "disabled": false,
      "chart": {
        "paused": false,
        "crosshair": false,
        "cursorX": null,
        "dragging": false,
        "layout": null,
        "data": []
      },
      "log": {
        "active": false,
        "buffer": [],
        "startTime": null,
        "count": 0
      },
      "chartReg": 109,
      "chartName": "ZSW1 + actual (40110-40111) [109]",
      "logFile": "log_ZSW1_actual_40110_40111_.txt"
    },
    {
      "name": "Diagnostics (40340-40349)",
      "fc": 3,
      "addr": 339,
      "qty": 10,
      "slaveId": 1,
      "interval": 1000,
      "disabled": false,
      "chart": {
        "paused": false,
        "crosshair": false,
        "cursorX": null,
        "dragging": false,
        "layout": null,
        "data": []
      },
      "log": {
        "active": false,
        "buffer": [],
        "startTime": null,
        "count": 0
      },
      "chartReg": 339,
      "chartName": "Diagnostics (40340-40349) [339]",
      "logFile": "log_Diagnostics_40340_40349_.txt"
    },
    {
      "name": "Faults (40400-40403)",
      "fc": 3,
      "addr": 399,
      "qty": 4,
      "slaveId": 1,
      "interval": 2000,
      "disabled": false,
      "chart": {
        "paused": false,
        "crosshair": false,
        "cursorX": null,
        "dragging": false,
        "layout": null,
        "data": []
      },
      "log": {
        "active": false,
        "buffer": [],
        "startTime": null,
        "count": 0
      },
      "chartReg": 399,
      "chartName": "Faults (40400-40403) [399]",
      "logFile": "log_Faults_40400_40403_.txt"
    },
    {
      "name": "Reference speed p2000 (40324)",
      "fc": 3,
      "addr": 323,
      "qty": 1,
      "slaveId": 1,
      "interval": 10000,
      "disabled": false,
      "chart": {
        "paused": false,
        "crosshair": false,
        "cursorX": null,
        "dragging": false,
        "layout": null,
        "data": []
      },
      "log": {
        "active": false,
        "buffer": [],
        "startTime": null,
        "count": 0
      },
      "chartReg": 323,
      "chartName": "Reference speed p2000 (40324) [323]",
      "logFile": "log_Reference_speed_p2000_40324_.txt"
    }
  ],
  "activePoll": 0,
  "condColors": {},
  "scaling": {},
  "valueNames": {},
  "chartSeries": [],
  "slaveBlocks": [],
  "dashTheme": "modern",
  "dashFx": true,
  "dashBgColor": "#0d1117",
  "dashPages": [
    {
      "id": 1,
      "name": "G120",
      "elements": [
        {
          "id": 1,
          "value": 0,
          "type": "statictext",
          "x": 20,
          "y": 10,
          "w": 840,
          "h": 30,
          "text": "Fan F-7  ·  Siemens SINAMICS G120 CU240E-2  ·  Modbus RTU, read-only",
          "fontSize": 20,
          "bold": true,
          "color": "#e6eef8"
        },
        {
          "id": 2,
          "value": 0,
          "type": "drive",
          "x": 20,
          "y": 50,
          "w": 300,
          "h": 150,
          "label": "F-7 G120",
          "unit": "rpm",
          "min": 0,
          "max": 1500,
          "step": 50,
          "powerUnit": "kW",
          "fbTimeout": 10,
          "startVal": 1,
          "stopVal": 0,
          "resetVal": 1,
          "resetBack": 0,
          "resetMs": 1000,
          "items": [
            {
              "role": "run",
              "name": "RUN",
              "sourceType": "register",
              "slaveId": 1,
              "regType": "holdingRegisters",
              "address": 109,
              "bit": 2
            },
            {
              "role": "ready",
              "name": "READY",
              "sourceType": "register",
              "slaveId": 1,
              "regType": "holdingRegisters",
              "address": 109,
              "bit": 1
            },
            {
              "role": "atSp",
              "name": "ATSP",
              "sourceType": "register",
              "slaveId": 1,
              "regType": "holdingRegisters",
              "address": 109,
              "bit": 8
            },
            {
              "role": "warn",
              "name": "WARN",
              "sourceType": "register",
              "slaveId": 1,
              "regType": "holdingRegisters",
              "address": 109,
              "bit": 7
            },
            {
              "role": "fault",
              "name": "FAULT",
              "sourceType": "register",
              "slaveId": 1,
              "regType": "holdingRegisters",
              "address": 109,
              "bit": 3
            },
            {
              "role": "hand",
              "name": "HAND"
            },
            {
              "role": "faultCode",
              "name": "CODE",
              "sourceType": "tag",
              "tagName": "Fault_0"
            },
            {
              "role": "freq",
              "name": "HZ",
              "sourceType": "tag",
              "tagName": "Frequency_Hz"
            },
            {
              "role": "current",
              "name": "A",
              "sourceType": "tag",
              "tagName": "Current_A"
            },
            {
              "role": "power",
              "name": "P",
              "sourceType": "tag",
              "tagName": "Power_kW"
            },
            {
              "role": "speedAct",
              "name": "SPEED",
              "sourceType": "tag",
              "tagName": "Speed_rpm"
            },
            {
              "role": "ref",
              "name": "REF"
            },
            {
              "role": "hours",
              "name": "H"
            },
            {
              "role": "runCmd",
              "name": "RUN CMD"
            },
            {
              "role": "resetCmd",
              "name": "RESET"
            }
          ]
        },
        {
          "id": 3,
          "value": 0,
          "type": "text",
          "x": 20,
          "y": 210,
          "w": 145,
          "h": 56,
          "label": "Speed 40341",
          "unit": "rpm",
          "decimals": 0,
          "fontSize": 24,
          "color": "#00d4aa",
          "sourceType": "tag",
          "tagName": "Speed_rpm"
        },
        {
          "id": 4,
          "value": 0,
          "type": "text",
          "x": 175,
          "y": 210,
          "w": 145,
          "h": 56,
          "label": "Setpoint 40340",
          "unit": "rpm",
          "decimals": 0,
          "fontSize": 24,
          "color": "#9fb3cc",
          "sourceType": "tag",
          "tagName": "Speed_SP_rpm"
        },
        {
          "id": 5,
          "value": 0,
          "type": "text",
          "x": 20,
          "y": 274,
          "w": 145,
          "h": 56,
          "label": "Torque 40346",
          "unit": "Nm",
          "decimals": 1,
          "fontSize": 24,
          "color": "#00d4aa",
          "sourceType": "tag",
          "tagName": "Torque_Nm"
        },
        {
          "id": 6,
          "value": 0,
          "type": "text",
          "x": 175,
          "y": 274,
          "w": 145,
          "h": 56,
          "label": "DC link 40344",
          "unit": "V",
          "decimals": 0,
          "fontSize": 24,
          "color": "#00d4aa",
          "sourceType": "tag",
          "tagName": "DC_Link_V"
        },
        {
          "id": 7,
          "value": 0,
          "type": "bitword",
          "x": 340,
          "y": 50,
          "w": 300,
          "h": 330,
          "label": "ZSW1 40110",
          "sourceType": "register",
          "slaveId": 1,
          "regType": "holdingRegisters",
          "address": 109,
          "wsize": 16,
          "wordOrder": "hl",
          "view": "all",
          "bitCols": 1,
          "showNums": true,
          "emptyText": "",
          "bits": [
            {
              "bit": 0,
              "name": "Ready for switching on",
              "kind": "ok"
            },
            {
              "bit": 1,
              "name": "Ready",
              "kind": "ok"
            },
            {
              "bit": 2,
              "name": "Operation enabled",
              "kind": "ok"
            },
            {
              "bit": 3,
              "name": "Fault active",
              "kind": "alarm"
            },
            {
              "bit": 4,
              "name": "OFF2 inactive",
              "kind": "ok"
            },
            {
              "bit": 5,
              "name": "OFF3 inactive",
              "kind": "ok"
            },
            {
              "bit": 6,
              "name": "Switching on inhibited",
              "kind": "warn"
            },
            {
              "bit": 7,
              "name": "Alarm active",
              "kind": "warn"
            },
            {
              "bit": 8,
              "name": "Speed deviation in tolerance",
              "kind": "info"
            },
            {
              "bit": 9,
              "name": "Master control requested",
              "kind": "info"
            },
            {
              "bit": 10,
              "name": "Comparison speed reached",
              "kind": "info"
            },
            {
              "bit": 11,
              "name": "Current / torque limit reached",
              "kind": "warn"
            },
            {
              "bit": 12,
              "name": "Holding brake open",
              "kind": "info"
            },
            {
              "bit": 13,
              "name": "No motor overtemperature alarm",
              "kind": "ok"
            },
            {
              "bit": 14,
              "name": "Motor rotates clockwise",
              "kind": "info"
            }
          ]
        },
        {
          "id": 8,
          "value": 0,
          "type": "text",
          "x": 660,
          "y": 50,
          "w": 200,
          "h": 56,
          "label": "Actual 40111",
          "unit": "% p2000",
          "decimals": 1,
          "fontSize": 24,
          "color": "#00d4aa",
          "sourceType": "tag",
          "tagName": "Actual_pct"
        },
        {
          "id": 9,
          "value": 0,
          "type": "text",
          "x": 660,
          "y": 116,
          "w": 200,
          "h": 56,
          "label": "Output voltage 40343",
          "unit": "V",
          "decimals": 0,
          "fontSize": 24,
          "color": "#00d4aa",
          "sourceType": "tag",
          "tagName": "Output_V"
        },
        {
          "id": 10,
          "value": 0,
          "type": "text",
          "x": 660,
          "y": 182,
          "w": 200,
          "h": 56,
          "label": "Energy 40348",
          "unit": "kWh",
          "decimals": 0,
          "fontSize": 24,
          "color": "#9fb3cc",
          "sourceType": "tag",
          "tagName": "Energy_kWh"
        },
        {
          "id": 11,
          "value": 0,
          "type": "multistate",
          "x": 660,
          "y": 248,
          "w": 200,
          "h": 56,
          "label": "Control 40349",
          "states": "0=Manual:#f0c040,1=Auto:#3fd28a",
          "sourceType": "tag",
          "tagName": "Control_Auto"
        },
        {
          "id": 12,
          "value": 0,
          "type": "text",
          "x": 660,
          "y": 312,
          "w": 200,
          "h": 56,
          "label": "Fault 40400",
          "unit": "",
          "decimals": 0,
          "fontSize": 24,
          "color": "#9fb3cc",
          "sourceType": "tag",
          "tagName": "Fault_0"
        },
        {
          "id": 13,
          "value": 0,
          "type": "multitend",
          "x": 20,
          "y": 395,
          "w": 840,
          "h": 145,
          "label": "Speed (rpm) and current (A)",
          "maxPoints": 1200,
          "decimals": 1,
          "sampleMs": 1000,
          "items": [
            {
              "name": "Speed 40341",
              "sourceType": "tag",
              "tagName": "Speed_rpm",
              "color": "#00d4aa",
              "value": 0
            },
            {
              "name": "Current 40345",
              "sourceType": "tag",
              "tagName": "Current_A",
              "color": "#f0c040",
              "value": 0
            }
          ],
          "yMin": 0,
          "yMax": 1500
        }
      ]
    }
  ],
  "tags": [
    {
      "name": "ZSW1",
      "type": "register",
      "slaveId": 1,
      "regType": "holdingRegisters",
      "address": 109,
      "dataType": "uint16",
      "wordOrder": "big",
      "description": "status word 1 (40110, wire 109)",
      "scale": 1,
      "offset": 0
    },
    {
      "name": "Actual_pct",
      "type": "register",
      "slaveId": 1,
      "regType": "holdingRegisters",
      "address": 110,
      "dataType": "int16",
      "wordOrder": "big",
      "description": "main actual value, 4000 hex = 100 % of p2000 (40111, wire 110)",
      "scale": 0.006103515625,
      "offset": 0
    },
    {
      "name": "Speed_SP_rpm",
      "type": "register",
      "slaveId": 1,
      "regType": "holdingRegisters",
      "address": 339,
      "dataType": "int16",
      "wordOrder": "big",
      "description": "r0020 speed setpoint rpm (40340, wire 339)",
      "scale": 1,
      "offset": 0
    },
    {
      "name": "Speed_rpm",
      "type": "register",
      "slaveId": 1,
      "regType": "holdingRegisters",
      "address": 340,
      "dataType": "int16",
      "wordOrder": "big",
      "description": "r0022 speed actual rpm (40341, wire 340)",
      "scale": 1,
      "offset": 0
    },
    {
      "name": "Frequency_Hz",
      "type": "register",
      "slaveId": 1,
      "regType": "holdingRegisters",
      "address": 341,
      "dataType": "int16",
      "wordOrder": "big",
      "description": "r0024 output frequency, x 100 (40342, wire 341)",
      "scale": 0.01,
      "offset": 0
    },
    {
      "name": "Output_V",
      "type": "register",
      "slaveId": 1,
      "regType": "holdingRegisters",
      "address": 342,
      "dataType": "int16",
      "wordOrder": "big",
      "description": "r0025 output voltage V (40343, wire 342)",
      "scale": 1,
      "offset": 0
    },
    {
      "name": "DC_Link_V",
      "type": "register",
      "slaveId": 1,
      "regType": "holdingRegisters",
      "address": 343,
      "dataType": "int16",
      "wordOrder": "big",
      "description": "r0026 DC link voltage V (40344, wire 343)",
      "scale": 1,
      "offset": 0
    },
    {
      "name": "Current_A",
      "type": "register",
      "slaveId": 1,
      "regType": "holdingRegisters",
      "address": 344,
      "dataType": "int16",
      "wordOrder": "big",
      "description": "r0027 current actual, x 100 (40345, wire 344)",
      "scale": 0.01,
      "offset": 0
    },
    {
      "name": "Torque_Nm",
      "type": "register",
      "slaveId": 1,
      "regType": "holdingRegisters",
      "address": 345,
      "dataType": "int16",
      "wordOrder": "big",
      "description": "r0031 torque actual, x 100 (40346, wire 345)",
      "scale": 0.01,
      "offset": 0
    },
    {
      "name": "Power_kW",
      "type": "register",
      "slaveId": 1,
      "regType": "holdingRegisters",
      "address": 346,
      "dataType": "int16",
      "wordOrder": "big",
      "description": "r0032 active power, x 100 (40347, wire 346)",
      "scale": 0.01,
      "offset": 0
    },
    {
      "name": "Energy_kWh",
      "type": "register",
      "slaveId": 1,
      "regType": "holdingRegisters",
      "address": 347,
      "dataType": "int16",
      "wordOrder": "big",
      "description": "r0039 energy kWh (40348, wire 347)",
      "scale": 1,
      "offset": 0
    },
    {
      "name": "Control_Auto",
      "type": "register",
      "slaveId": 1,
      "regType": "holdingRegisters",
      "address": 348,
      "dataType": "int16",
      "wordOrder": "big",
      "description": "r0807 control: manual / auto (40349, wire 348)",
      "scale": 1,
      "offset": 0
    },
    {
      "name": "Fault_0",
      "type": "register",
      "slaveId": 1,
      "regType": "holdingRegisters",
      "address": 399,
      "dataType": "int16",
      "wordOrder": "big",
      "description": "r0947[0] fault number (40400, wire 399)",
      "scale": 1,
      "offset": 0
    },
    {
      "name": "p2000_rpm",
      "type": "register",
      "slaveId": 1,
      "regType": "holdingRegisters",
      "address": 323,
      "dataType": "int16",
      "wordOrder": "big",
      "description": "p2000 reference speed rpm (40324, wire 323)",
      "scale": 1,
      "offset": 0
    }
  ],
  "script": "",
  "scriptInterval": "1000",
  "historianLogging": {
    "registers": [],
    "tags": []
  },
  "saved": "2026-11-08T12:00:00.000Z"
}