Carlo Gavazzi EM340 — Modbus register map

EM340-DIN AV2 3 X S1 PF B, three-phase energy meter · RS-485 Modbus RTU

Registers76 (74 polled, 2 write-only)
Source documentEM300 Series and ET300 Series COMMUNICATION PROTOCOL, Version 2 Revision 17 (July 05, 2021) - file EM330_EM340_ET330_ET340_CP.pdf
Reviewed2026-11-09 · ModbusManager engineering
OrderSAMPLE

How to read this map

Traps in this device

Check on site

Files

Poll blocks and intervals

Values that change all the time are read every second; settings and identification only change when someone reconfigures the device, so they are read rarely. This keeps the RS-485 line free for the live values and for other devices on the same line.

BlockFCAddressWordsInterval
Live measurementsFC40000h–0031h501 s
Live measurementsFC40032h–0033h21 s
Energy and demandFC40034h–0049h221 s
Energy and demandFC4004Eh–0051h41 s
Energy and demandFC4011Ah–011Bh21 s
Energy with 3 decimalsFC40400h–040Fh165 s
TariffFC31200h–1201h210 s
Identification (read alone)FC3000Bh160 s
IdentificationFC40302h–0303h260 s
SetupFC31002h–1006h560 s
SetupFC31010h–1011h260 s
SetupFC31105h160 s
RS-485 settingsFC32000h–2004h560 s
IdentificationFC45000h–5006h760 s
IdentificationFC45010h160 s

At 9600 baud these intervals use about 30 % of the line per meter; reading every block every second would use about 61 %. To read a value faster, change the interval of its block in ModbusManager Pro.

Dashboard

The workspace's dashboard in ModbusManager Pro, against a simulator of this meter.

Dashboard pageDashboard page

Register map

Address = wire address (0-based, in the Modbus frame). Doc = the number printed in the document. Value = raw × scale + offset. Page = page of the source document.

RegisterFCDocAddressTypeScaleUnitPageStatusNote
Live measurements
V L1-N
Phase 1 to neutral voltage
V_L1_N
FC43000010
0000h
int32 2w LSW first0.1V9checkedSame value also in Table 2.6-1.
V L2-N
Phase 2 to neutral voltage
V_L2_N
FC43000032
0002h
int32 2w LSW first0.1V9checkedSame value also in Table 2.6-1.
V L3-N
Phase 3 to neutral voltage
V_L3_N
FC43000054
0004h
int32 2w LSW first0.1V9checkedSame value also in Table 2.6-1.
V L1-L2
Line voltage L1-L2
V_L1_L2
FC43000076
0006h
int32 2w LSW first0.1V9checkedSame value also in Table 2.6-1.
V L2-L3
Line voltage L2-L3
V_L2_L3
FC43000098
0008h
int32 2w LSW first0.1V9checkedSame value also in Table 2.6-1.
V L3-L1
Line voltage L3-L1
V_L3_L1
FC430001110
000Ah
int32 2w LSW first0.1V9checkedSame value also in Table 2.6-1.
A L1
Phase 1 current
A_L1
FC430001312
000Ch
int32 2w LSW first0.001A9checkedSame value also in Table 2.6-1.
A L2
Phase 2 current
A_L2
FC430001514
000Eh
int32 2w LSW first0.001A9checkedSame value also in Table 2.6-1.
A L3
Phase 3 current
A_L3
FC430001716
0010h
int32 2w LSW first0.001A9checkedSame value also in Table 2.6-1.
W L1
Phase 1 active power (negative = exported)
kW_L1
FC430001918
0012h
int32 2w LSW first0.1W9checkedSame value also in Table 2.6-1.
W L2
Phase 2 active power
kW_L2
FC430002120
0014h
int32 2w LSW first0.1W9checkedSame value also in Table 2.6-1.
W L3
Phase 3 active power
kW_L3
FC430002322
0016h
int32 2w LSW first0.1W9checkedSame value also in Table 2.6-1.
VA L1
Phase 1 apparent power
kVA_L1
FC430002524
0018h
int32 2w LSW first0.1VA9checkedSame value also in Table 2.6-1.
VA L2
Phase 2 apparent power
kVA_L2
FC430002726
001Ah
int32 2w LSW first0.1VA9checkedSame value also in Table 2.6-1.
VA L3
Phase 3 apparent power
kVA_L3
FC430002928
001Ch
int32 2w LSW first0.1VA9checkedSame value also in Table 2.6-1.
var L1
Phase 1 reactive power
kvar_L1
FC430003130
001Eh
int32 2w LSW first0.1var9checkedSame value also in Table 2.6-1.
var L2
Phase 2 reactive power
kvar_L2
FC430003332
0020h
int32 2w LSW first0.1var9checkedSame value also in Table 2.6-1.
var L3
Phase 3 reactive power
kvar_L3
FC430003534
0022h
int32 2w LSW first0.1var9checkedSame value also in Table 2.6-1.
V L-N sys
System phase-neutral voltage
V_LN_sys
FC430003736
0024h
int32 2w LSW first0.1V9checkedSame value also in Table 2.6-1.
V L-L sys
System line-line voltage
V_LL_sys
FC430003938
0026h
int32 2w LSW first0.1V9checkedSame value also in Table 2.6-1.
W sys
System active power (negative = exported)
kW_sys
FC430004140
0028h
int32 2w LSW first0.1W9checkedSame value also in Table 2.6-1.
VA sys
System apparent power
kVA_sys
FC430004342
002Ah
int32 2w LSW first0.1VA9checkedSame value also in Table 2.6-1.
var sys
System reactive power
kvar_sys
FC430004544
002Ch
int32 2w LSW first0.1var9checkedSame value also in Table 2.6-1.
PF L1
Power factor L1
PF_L1
FC430004746
002Eh
int160.0019checkedINT16 in Table 2.4-1 (INT32 in Table 2.6-1). Sign convention for C/L depends on measurement mode.
PF L2
Power factor L2
PF_L2
FC430004847
002Fh
int160.0019checkedINT16 in Table 2.4-1 (INT32 in Table 2.6-1). Sign convention for C/L depends on measurement mode.
PF L3
Power factor L3
PF_L3
FC430004948
0030h
int160.0019checkedINT16 in Table 2.4-1 (INT32 in Table 2.6-1). Sign convention for C/L depends on measurement mode.
PF sys
Power factor sys
PF_sys
FC430005049
0031h
int160.0019checkedINT16 in Table 2.4-1 (INT32 in Table 2.6-1). Sign convention for C/L depends on measurement mode.
Phase sequence
Phase sequence: 0 = L1-L2-L3, 1 = L1-L3-L2
Phase_seq
FC430005150
0032h
int1619checkedMeaningful only in a 3-phase system.
Hz
Frequency
Hz
FC430005251
0033h
int160.1Hz9checked
Energy and demand
kWh (+) TOT
Total imported active energy
kWh_imp
FC430005352
0034h
int32 2w LSW first0.1kWh9checked0.1 kWh resolution; see Table 2.5-1 for 3-decimal values.
kvarh (+) TOT
Total imported (positive) reactive energy
kvarh_imp
FC430005554
0036h
int32 2w LSW first0.1kvarh9checked0.1 kWh resolution; see Table 2.5-1 for 3-decimal values. Tariff/partial rows depend on option.
kW dmd
Active power demand
kW_dmd
FC430005756
0038h
int32 2w LSW first0.1W9checked0.1 kWh resolution; see Table 2.5-1 for 3-decimal values. Tariff/partial rows depend on option.
kW dmd peak
Active power demand peak
kW_dmd_peak
FC430005958
003Ah
int32 2w LSW first0.1W9checked0.1 kWh resolution; see Table 2.5-1 for 3-decimal values. Tariff/partial rows depend on option.
kWh (+) PARTIAL
Partial imported active energy
kWh_imp_partial
FC430006160
003Ch
int32 2w LSW first0.1kWh9checked0.1 kWh resolution; see Table 2.5-1 for 3-decimal values. Tariff/partial rows depend on option.
kvarh (+) PARTIAL
Partial imported reactive energy
kvarh_imp_partial
FC430006362
003Eh
int32 2w LSW first0.1kvarh9checked0.1 kWh resolution; see Table 2.5-1 for 3-decimal values. Tariff/partial rows depend on option.
kWh (+) L1
Imported active energy phase 1
kWh_imp_L1
FC430006564
0040h
int32 2w LSW first0.1kWh9checked0.1 kWh resolution; see Table 2.5-1 for 3-decimal values. Tariff/partial rows depend on option.
kWh (+) L2
Imported active energy phase 2
kWh_imp_L2
FC430006766
0042h
int32 2w LSW first0.1kWh9checked0.1 kWh resolution; see Table 2.5-1 for 3-decimal values. Tariff/partial rows depend on option.
kWh (+) L3
Imported active energy phase 3
kWh_imp_L3
FC430006968
0044h
int32 2w LSW first0.1kWh9checked0.1 kWh resolution; see Table 2.5-1 for 3-decimal values. Tariff/partial rows depend on option.
kWh (+) t1
Imported active energy tariff 1
kWh_imp_t1
FC430007170
0046h
int32 2w LSW first0.1kWh9checked0.1 kWh resolution; see Table 2.5-1 for 3-decimal values. Tariff/partial rows depend on option.
kWh (+) t2
Imported active energy tariff 2
kWh_imp_t2
FC430007372
0048h
int32 2w LSW first0.1kWh9checked0.1 kWh resolution; see Table 2.5-1 for 3-decimal values. Tariff/partial rows depend on option.
kWh (-) TOT
Total exported active energy
kWh_exp
FC430007978
004Eh
int32 2w LSW first0.1kWh9checked0.1 kWh resolution; see Table 2.5-1 for 3-decimal values. Tariff/partial rows depend on option.
kvarh (-) TOT
Total exported (negative) reactive energy
kvarh_exp
FC430008180
0050h
int32 2w LSW first0.1kvarh9checked0.1 kWh resolution; see Table 2.5-1 for 3-decimal values. Tariff/partial rows depend on option.
Energy and demand (second table)
W dmd
Active power demand (grouped-by-phase table)
kW_dmd_2
FC4300283282
011Ah
int32 2w LSW first0.1W12checkedSame value as kW dmd at 0038h, in the second measurement table (Table 2.6-1, p.12).
Energy with 3 decimals (integer + decimal part)
kWh (+) TOT - INTeger part
Imported active energy, integer kWh
kWh_imp_int
FC43010251024
0400h
int32 2w LSW first1kWh11checkedTable 2.5-1: EM340 made from 1 Oct 2018 only. Total = integer part + decimal part x 0.001 (decimal part holds 0..999). Format printed INT32; LSW first.
kWh (+) TOT - DECimal part
Imported active energy, fraction in 1/1000 kWh
kWh_imp_dec
FC43010271026
0402h
int32 2w LSW first0.001kWh11checkedTable 2.5-1: EM340 made from 1 Oct 2018 only. Total = integer part + decimal part x 0.001 (decimal part holds 0..999). Format printed INT32; LSW first.
kvarh (+) TOT - INTeger part
Imported reactive energy, integer kvarh
kvarh_imp_int
FC43010291028
0404h
int32 2w LSW first1kvarh11checkedTable 2.5-1: EM340 made from 1 Oct 2018 only. Total = integer part + decimal part x 0.001 (decimal part holds 0..999). Format printed INT32; LSW first.
kvarh (+) TOT - DECimal part
Imported reactive energy, fraction in 1/1000 kvarh
kvarh_imp_dec
FC43010311030
0406h
int32 2w LSW first0.001kvarh11checkedTable 2.5-1: EM340 made from 1 Oct 2018 only. Total = integer part + decimal part x 0.001 (decimal part holds 0..999). Format printed INT32; LSW first.
kWh (-) TOT - INTeger part
Exported active energy, integer kWh
kWh_exp_int
FC43010331032
0408h
int32 2w LSW first1kWh11checkedTable 2.5-1: EM340 made from 1 Oct 2018 only. Total = integer part + decimal part x 0.001 (decimal part holds 0..999). Format printed INT32; LSW first.
kWh (-) TOT - DECimal part
Exported active energy, fraction in 1/1000 kWh
kWh_exp_dec
FC43010351034
040Ah
int32 2w LSW first0.001kWh11checkedTable 2.5-1: EM340 made from 1 Oct 2018 only. Total = integer part + decimal part x 0.001 (decimal part holds 0..999). Format printed INT32; LSW first.
kvarh (-) TOT - INTeger part
Exported reactive energy, integer kvarh
kvarh_exp_int
FC43010371036
040Ch
int32 2w LSW first1kvarh11checkedTable 2.5-1: EM340 made from 1 Oct 2018 only. Total = integer part + decimal part x 0.001 (decimal part holds 0..999). Format printed INT32; LSW first.
kvarh (-) TOT - DECimal part
Exported reactive energy, fraction in 1/1000 kvarh
kvarh_exp_dec
FC43010391038
040Eh
int32 2w LSW first0.001kvarh11checkedTable 2.5-1: EM340 made from 1 Oct 2018 only. Total = integer part + decimal part x 0.001 (decimal part holds 0..999). Format printed INT32; LSW first.
Identification
Carlo Gavazzi Controls identification code
Model ID; 341 for EM340-DIN AV2 3 X S1 PF B
ID_code
FC330001211
000Bh
uint16114checkedRead alone, one word per request (Table 2.8-1). EM340 returns 341 (Table 2.8-2).
Version code
Firmware version code (0=A, 1=B ...)
Version_code
FC4300771770
0302h
uint16113checked
Revision code
Firmware revision code
Revision_code
FC4300772771
0303h
uint16113checked
Serial number char 1
Serial number character 1 (ASCII in LSB)
SN_1
FC432048120480
5000h
uint16118checked
Serial number char 2
Serial number character 2 (ASCII in LSB)
SN_2
FC432048220481
5001h
uint16118checked
Serial number char 3
Serial number character 3 (ASCII in LSB)
SN_3
FC432048320482
5002h
uint16118checked
Serial number char 4
Serial number character 4 (ASCII in LSB)
SN_4
FC432048420483
5003h
uint16118checked
Serial number char 5
Serial number character 5 (ASCII in LSB)
SN_5
FC432048520484
5004h
uint16118checked
Serial number char 6
Serial number character 6 (ASCII in LSB)
SN_6
FC432048620485
5005h
uint16118checked
Serial number char 7
Serial number character 7 (ASCII in LSB)
SN_7
FC432048720486
5006h
uint16118checked
Production year
Production year
Production_year
FC432049720496
5010h
uint16118checkedEM340 made from Oct 2018 only.
Setup
Measuring system
0=3Pn, 1=3P, 2=2P (1P in revision notes)
Measuring_system
FC33040994098
1002h
uint16115checkedRead/write.
Current transformer ratio
CT ratio (value/10)
CT_ratio
FC33041004099
1003h
uint32 2w LSW first0.115checkedCT ratio x10: value 10 = CT 1.0 (Table 2.9-3). Read/write.
Voltage transformer ratio
VT ratio (value/10)
VT_ratio
FC33041024101
1005h
uint32 2w LSW first0.115checkedVT ratio x10: value 10 = VT 1.0 (Table 2.9-3). Read/write.
Integration time for dmd power
Demand integration time
Dmd_integration_time
FC3n/a4112
1010h
uint32 2w LSW first115mediumRange 1-30. The document gives no unit; minutes is likely, check on the meter.
Wrong connection (installing help) status
Bit flags for wiring errors
Wiring_status
FC33043584357
1105h
uint16116checkedBit0 wrong sequence, bit1-3 phase 1/2/3 inverted, bit4 L1-L2 exchanged, bit5 L1-L3, bit6 L2-L3, bit7 all exchanged.
Tariff
Tariff mode selection
0 = via digital inputs, 1 = via serial
Tariff_mode
FC33046094608
1200h
uint16117checkedRead/write.
Tariff number selection via serial comm.
Active tariff 1 or 2
Tariff_number
FC33046104609
1201h
uint16117checkedRead-only if 1200h=0.
RS-485 settings
RS485 instrument address
Modbus slave address 1..247
RS485_address
FC33081938192
2000h
uint16117checked1-247, default 1. Read/write.
RS485 baud rate
1=9.6k,2=19.2k,3=38.4k,4=57.6k,5=115.2k
RS485_baud
FC33081948193
2001h
uint16117checked1 = 9.6, 2 = 19.2, 3 = 38.4, 4 = 57.6, 5 = 115.2 kbps; default 1. Read/write.
RS485 parity
1=none, 2=even
RS485_parity
FC33081958194
2002h
uint16117checked1 = no parity (default), 2 = even. Read/write.
RS485 Stop bit
0/1 = 1 stop bit, 2 = 2 stop bits (only if even parity)
RS485_stop_bits
FC33081968195
2003h
uint16117checked0 = 1 stop bit, 1 = 1 (default), 2 = 2 (only with even parity). Read/write.
Max number of words readable with a single Modbus request
Read-only, 50
Max_words_per_request
FC33081978196
2004h
uint16117checkedAlways 50: the most words one request may read.
Commands (write only, not polled)
Reset partial/tariff meters and dmd
Write 1 to reset partial, tariff meters, kWdmd and peak
write31638516384
4000h
uint16117checkedWrite fn 06.
Reset total energy meters
Write 1; non-MID versions (X option) only
write31638616385
4001h
uint16117checkedWrite 1 to reset. Only on non-MID versions (X option).

Built from the vendor document listed above and checked by an engineer. The vendor document remains the authority; if the meter's firmware differs from the document version, re-check the rows marked in "Check on site". ModbusManager · modbusmanager.com