Every device. One tool. Pay once. Modbus · BACnet · Siemens S7 · one-time licence · also from us: BACManager ↗
// Device guide — Eastron

Eastron SDM630
Modbus Guide

Read voltage, current, power, power factor, frequency and energy from an Eastron SDM630 three-phase energy meter over Modbus RTU. This guide gives the full register map, FLOAT32 decoding, the FC04 input-register detail that trips people up, and how to get live data — and log it — with ModbusManager on Windows.

Download ModbusManager Pro (free trial) + demo workspace (.json)

Windows 10/11 · free 14-day Pro trial · open the .json workspace inside the app

// register map

SDM630 Modbus register list

Every measurement is a FLOAT32 (two registers), read with function code 04. The left column is the 1-based number from the Eastron protocol; the second is the 0-based address that goes in the request frame.

RegisterAddressMeasurementUnit
300010x0000Voltage L1-NV
300030x0002Voltage L2-NV
300050x0004Voltage L3-NV
300070x0006Current L1A
300090x0008Current L2A
300110x000ACurrent L3A
300130x000CActive power L1W
300150x000EActive power L2W
300170x0010Active power L3W
300190x0012Apparent power L1VA
300210x0014Apparent power L2VA
300230x0016Apparent power L3VA
300250x0018Reactive power L1VAr
300270x001AReactive power L2VAr
300290x001CReactive power L3VAr
300310x001EPower factor L1—
300330x0020Power factor L2—
300350x0022Power factor L3—
300430x002AAverage voltage L-NV
300490x0030Sum of line currentsA
300530x0034Total active powerW
300570x0038Total apparent powerVA
300610x003CTotal reactive powerVAr
300630x003ETotal power factor—
300710x0046FrequencyHz
300730x0048Import active energykWh
300750x004AExport active energykWh
300770x004CImport reactive energykVArh
300790x004EExport reactive energykVArh
302010x00C8Voltage L1-L2V
302030x00CAVoltage L2-L3V
302050x00CCVoltage L3-L1V
302250x00E0Neutral currentA
302350x00EAVoltage THD L1-N%
302370x00ECVoltage THD L2-N%
302390x00EEVoltage THD L3-N%
303430x0156Total active energy (import + export)kWh
One request may ask for at most 40 values (80 registers), or the meter answers with an exception. 30001–30080 covers everything from voltage to reactive energy in two reads.

The protocol document lists further demand, per-phase energy and current-THD registers; the table above is what installers and integrators poll in practice. Configuration (baud rate, address, CT ratio on the MCT) lives in holding registers, read with FC03 and written with FC16.

SDM630MCT — the CT-operated variant

The SDM630MCT measures through external current transformers instead of direct connection, but speaks the same Modbus: FC04, FLOAT32 pairs, and the measurement addresses above are identical. The practical differences are the CT ratio — set from the meter’s set-up menu (or the holding registers listed in the MCT protocol document) so the reported currents and powers are already scaled to primary values — and slightly different energy-resolution behaviour on some firmware. If your SDM630MCT readings look off by a constant factor, the CT ratio is the first thing to check. The free workspace on this page works with the MCT unchanged.

// one value, by hand

Decode an SDM630 reading yourself

What actually goes over the RS-485 line when you read the L1 voltage from meter address 1.

BytesMeaning
Request
01 04 00 00 00 02 71 CB
slave 1, FC04, address 0x0000 (register 30001), 2 registers, CRC
Response
01 04 04 43 66 66 66 A5 95
slave 1, FC04, 4 data bytes, value, CRC
Value
0x43666666
IEEE 754 float, high word first = 230.4 V

Frequency works the same way at address 0x0046: request 01 04 00 46 00 02 90 1E, a 50.00 Hz answer is 01 04 04 42 48 00 00 6F EA. If you get 42 48 00 00 where you expected a power factor, you are reading 30071 — frequency — instead of 30063. And if the four data bytes come back as 66 66 43 66, your software has the word order the wrong way round: the SDM630 sends the high word first.

// about the SDM630

The reference 3-phase meter

The SDM630 register layout is so widely used that other meters clone it — learn it once and you can read many devices.

Eastron’s SDM630 is the most widely deployed three-phase Modbus energy meter in the European prosumer and installer market — MID-certified, direct 100 A connection (or CT version), and around 100 Modbus registers covering everything from per-phase voltage to total energy. Its register map has become the de facto reference: the SDM630MCT and SDM630-TCP variants share it, and many Carlo Gavazzi and clone meters follow the same FLOAT32 layout. If you can read an SDM630, you can read most three-phase Modbus meters.

// download the demo

Ready-made SDM630 workspace

A free ModbusManager Pro workspace with the SDM630 register map already set up: Float32 tags and an energy-meter dashboard. Open it and point it at your meter.

The workspace polls input registers from 30001 (address 0, FC04) and decodes voltage, current, power, power factor and frequency as 32-bit floats — no scripting, no manual word-pairing. Every value lands on a clean dashboard ready to read. Set your meter’s slave ID and connection, and you have live data in seconds.

Open in ModbusManager Pro · 📋 Workspace → open · needs the Float32 tag type (v1.6+)

// connection settings

Modbus settings

Set these from the meter’s front panel (SET menu), then match them in ModbusManager.

SettingTypical value
ProtocolModbus RTU (2-wire RS-485)
Baud rate9600 (also 2400/4800/19200/38400)
ParityNone (1 stop bit) — default
Node address1–247 (set on meter)
Function code (measurements)04 — input registers
Function code (config)03 read / 16 write — holding registers
Data typeFLOAT32 (2 registers, big-endian)

Baud rate is not only a setup detail — it caps how often a whole line of meters can be read. At 9600 baud a 10-register read of one SDM630 costs roughly 52 ms, so twenty meters on the same pair need about a second for one full pass. See for the timing per baud rate and how to pick an interval that holds.

// how to read it

Read an SDM630 in three steps

From wiring to live values in a few minutes.

Step 1
Connect
Wire RS-485 A (+) and B (-) to the meter’s comm terminals with 120 Ω shielded twisted pair. In ModbusManager pick RTU with the meter’s baud rate (default 9600), parity and slave address.
Step 2
Poll & decode
Add a poll on input registers (FC04) starting at address 0 (register 30001). Set the display type to FLOAT32 so each register pair becomes a real value. With FC03 the meter still answers, but from its holding registers: address 0 is then 40001, the demand time, not the L1 voltage — measurements are input registers.
Step 3
Visualise & log
Map the values to a dashboard for a live panel, log them to the Historian for energy studies, or set alarms on over-voltage or over-current.
// why modbusmanager

A practical tool for energy meters

ModbusManager reads any SDM630 register directly, with built-in FLOAT32 decoding so you do not combine register pairs by hand, and a serial monitor to see every frame. The Standard edition ($49) covers polling, scaling and the serial monitor. The Pro edition ($119) adds drag-and-drop Modbus HMI software, a data logging Historian with CSV export for energy and load profiling, and an alarm system — all running locally on Windows, with no SCADA server or cloud account.

// frequently asked questions

SDM630 Modbus — FAQ

What function code does the SDM630 use?+
The SDM630 measurement values are input registers, read with Modbus function code 04 (not 03). Configuration parameters use holding registers with FC03 read and FC16 write. Reading the same address with FC03 does not fail: it reads the holding register there, a setting (at address 0 that is 40001, the demand time), not the measurement. Set your tool to FC04 for live values.
What format are SDM630 registers?+
Every measurement is a 32-bit IEEE 754 float spanning two consecutive registers, high word first (big-endian word order). There are no integer-with-scale-factor registers in the measurement area, so always read two registers per value and decode as FLOAT32.
What Modbus settings does the SDM630 use?+
The SDM630 is a Modbus RTU slave over 2-wire RS-485. Baud rate is selectable (2400, 4800, 9600, 19200, 38400), set from the front panel along with the node address and parity. A common default is 9600 baud, no parity, but check the meter's display.
Can I read the SDM630 register map with other meters?+
Yes. The SDM630 layout is the de facto reference for three-phase energy meters. Eastron variants (SDM630MCT, SDM630-TCP) and many Carlo Gavazzi meters follow the same FLOAT32, two-register-per-value pattern for voltage, current and power, though some addresses differ.
Can I log SDM630 energy data to a file?+
Yes. With ModbusManager Pro you can log any SDM630 register to a local Historian, view it as a trend chart and export to CSV - useful for energy studies, sub-billing and PV self-consumption analysis without a SCADA system.
// more than one meter?

Several SDM630s, one register map

One SDM630 is easy. Ten of them on the same RS-485 line, read by a PLC that has a single Modbus connection, is a different job. ModbusManager Pro can poll every meter and republish just the values you need — total active power, per-phase currents, energy counters — as one common register map the PLC reads in a single request. The FLOAT32 pairs stay floats, or get scaled into integers if that is what the PLC block expects. The same rows can go to MQTT and Home Assistant too — see Modbus to MQTT, with a free SDM630 workspace.

Modbus gateway software →

Read your SDM630 in minutes

Download ModbusManager and connect to your meter over RTU. Free 14-day Pro trial — no credit card, no cloud.

Download free trial See pricing

Windows 10/11 · Standard $49 · Pro $119 one-time