Build a live operator dashboard for your Siemens S7-1200 over Modbus TCP — without WinCC, a SCADA server or an OPC-UA license. Download the free demo project, run it on real hardware, and watch ModbusManager Pro display the PLC data live. Works the same with any other Modbus device. No PLC code at all? Read the CPU directly over S7 PUT/GET.
Demo: TIA Portal SCL + Pro workspace · tested on real S7-1200 · Modbus TCP
The demo turns a Siemens S7-1200 into a Modbus TCP server running a small simulated solar inverter — AC power, DC voltage and current, grid frequency, temperature, energy yield, battery state of charge and status bits. The PLC generates a realistic day curve so the data moves on its own.
ModbusManager Pro polls the PLC over Modbus TCP and shows everything on a drag-and-drop dashboard: gauges, KPI tiles, a power trend and status lamps — updating live. No WinCC runtime, no SCADA server, no per-tag licensing.
The Siemens PLC is just a relatable starting point. The same dashboard works with inverters, energy meters, VFDs and PLCs from any vendor, all on one screen.
S7-1200 (MB_SERVER, simulated inverter) → Modbus TCP, port 502 → ModbusManager Pro dashboard on Windows. One PC, no extra software.
Two ways to get it: a universal source package for any TIA version, or a ready-to-open TIA V15.1 project. Either way you import the PLC logic, open the workspace in ModbusManager Pro, connect, and you have a live dashboard.
Both need: an S7-1200 · ModbusManager Pro (14-day trial works). The workspace .json is also inside the source zip.
Holding registers, 0-based addressing, read with function code 03. 32-bit energy values use two registers (high word first).
| Addr | Value | Type | Scale | Unit |
|---|---|---|---|---|
| 0 | AC active power | INT | ÷10 | kW |
| 1 | DC voltage | INT | ÷1 | V |
| 2 | DC current | INT | ÷10 | A |
| 3 | Grid frequency | INT | ÷100 | Hz |
| 4 | Inverter temperature | INT | ÷10 | °C |
| 5–6 | Daily energy yield | U32 | ÷100 | kWh |
| 7–8 | Total energy yield | U32 | ÷1 | kWh |
| 9 | DC string 1 current | INT | ÷10 | A |
| 10 | Battery SOC | INT | ÷1 | % |
| 11 | Status word (bit0 run, bit2 derate, bit3 standby) | WORD | bits | — |
For a small system, a full WinCC or SCADA setup is expensive and heavy. ModbusManager Pro gives you a clean operator dashboard for a one-time 119 USD license — no runtime fees, no per-tag pricing, no server to maintain.
Because it speaks plain Modbus, it is not tied to Siemens. Put an S7-1200, a solar inverter, an energy meter and a VFD on the same dashboard, regardless of brand.
Commissioning and test benches, small operator panels, solar and energy monitoring, machine builders who want a quick visual without a SCADA project, and anyone with mixed-vendor Modbus devices.
Every device an S7-1200 talks to costs a connection, an MB_CLIENT call and its own configuration in TIA Portal. If the PLC only needs a handful of values from a dozen devices, ModbusManager Pro can do the collecting: it polls the devices, converts the data types, and serves one Modbus TCP slave that a single MB_CLIENT block reads. Setpoints written by the PLC are forwarded back to the right device.
Modbus gateway software →Reading a Rockwell drive from a Siemens PLC over Modbus RTU is common in mixed plants, and the first obstacle is always addressing rather than the protocol. Confirm the offset and scaling from a laptop before writing the MB_CLIENT logic.
PowerFlex 525 Modbus addressing →Download the free demo project and the ModbusManager Pro trial, and have a live Siemens dashboard running in minutes.
Windows 10/11 · 14-day trial · Pro $119 one-time
We use Google Analytics cookies to see how the site is used. You can accept or decline — declining keeps analytics off. See our Privacy Policy.