Every device. One tool. Pay once. Modbus · BACnet · Siemens S7 · one-time licence · also from us: BACManager ↗
// Device guide — ABB drives

ABB ACS580
Modbus RTU Guide

Read and control an ABB ACS580 variable frequency drive over Modbus RTU through its embedded fieldbus (EFB). This guide covers the ABB Drives profile — control word, status word, frequency reference and actual values — and how to test it all with ModbusManager on Windows, without a PLC or ABB commissioning software.

Download ModbusManager Pro See the data logger

Windows 10/11 · Modbus RTU & TCP · one-time license

// watch it

Fault 6681 while the panel is reading

ModbusManager Pro with an ABB ACS580 drive faceplate holding the command: running at 75 percent, status word bits ready, running and at setpoint ▶ 2:43
Settings, register 40001 = address 0, the control word, fault 6681 with 58.15 at Cw / Ref1 / Ref2, reset 0x04F6 → 0x0476, and the faceplate holding the command — against a simulated ACS580 over RTU.
// register map

ABB Drives profile registers

The core control and feedback registers in the ABB Drives profile. All are 16-bit holding registers, read with FC03 and written with FC06/FC16.

RegisterFunctionAccessSelected by / notes
40001Control WordR/W58.101 · start/stop/reset bits (ABB Drives profile)
40002Reference 1R/W58.102 · speed/frequency setpoint, 20000 = 100%
40003Reference 2R/W58.103 · second reference (e.g. torque), if used
40004Status WordR58.104 · ready/running/fault bits
40005Actual Value 1R58.105 · type set by 58.28 (speed or frequency by default)
40006Actual Value 2R58.106 · type set by 58.29
40007–40014Data I/O 7–14R/W58.107–58.114 · empty (None) until you point them at a parameter
ABB’s manual numbers these 400001–400014; it is the same registers. To read more values in one block, set 58.107–58.114 to the parameters you want — e.g. 01.06 Output frequency, 01.07 Motor current, 01.10 Motor torque, 01.14 Output power — and they appear at 40007 onward. ModbusManager takes the address on the wire, which is the register number minus 40001: the control word 40001 is address 0, the status word 40004 is address 3.

Any parameter can also be read directly. With 58.33 Addressing mode set to Mode 0, a 16-bit value sits at 400000 + 100 × group + index: 01.06 Output frequency is 400106, i.e. register 40106 in the numbering on this page. The 32-bit value of the same parameter is at 420000 + 200 × group + 2 × index (01.06 → 420212), which needs six-digit addressing. Other modes of 58.33 use other formulas — check it on the drive before you trust an address.

Looking these up to actually read them off a drive? Poll the status word (40004, address 3) live in about a minute — no PLC, no SCADA server. Read it live →
// about the ACS580 fieldbus

Embedded fieldbus, no extra hardware

The ACS580 — and its siblings ACH580, ACQ580 and the larger ACS880 — can act as a Modbus RTU slave straight out of the box.

ABB’s ACS580 general-purpose drive includes an embedded fieldbus interface (EFB) on its RS-485 terminals. With the protocol set to Modbus RTU, the drive becomes a Modbus slave you can read and control directly — useful for commissioning, fault-finding, second-hand drive checks and HMI integration without a PLC. Control uses the ABB Drives profile, where a control word starts and stops the drive and a reference sets the speed or frequency. The same approach applies across the ACx580 family and, with different parameter groups, the ACS880.

// download the monitor

Read-only monitoring workspace

A free ModbusManager Pro workspace that only reads the ACS580 — status word, output frequency and motor current — with ready/running/fault lamps on a dashboard. It writes nothing, so it cannot start the motor.

The workspace polls holding registers from 40004 (address 3) read-only (FC03), decodes the status word into ready / running / fault indicators and scales the actual values to frequency and current. There is no control word and no write poll — it is safe to load on a live drive for monitoring. Set your drive’s slave address and connection, and you see its state at a glance.

⚠ What 40005 and 40006 carry is set in the drive (Data I/O 58.105/58.106, type 58.28/58.29), and so is their scaling. This workspace assumes a typical setup (frequency, current). Verify against your drive and adjust the gains in the script if values look off. It also reads 40007 (address 6) as dio7_power_raw, which stays 0 until you set 58.107 Data I/O 7 to a power parameter such as 01.14 Output power; then 10000 = the power set in 46.04 Power scaling (1000 kW by default, so 0.1 kW per count).

Two steps: install the free 14-day Pro trial → open the .json workspace inside it (📋 Workspace → open). Read-only, no control — safe on a live drive.

// connection settings

Modbus settings

Configure the embedded fieldbus in parameter group 58, then match the same settings in ModbusManager.

SettingTypical value
ProtocolModbus RTU (RS-485, RTU only)
Command source (par. group 20)Embedded fieldbus (EFB)
Node address (par. 58.03)1–247
Baud rate (par. 58.04)9600 or 19200
Parity / stop bits (par. 58.05)8E1 or 8N2 (match both ends)
Function codes03 read, 06 / 16 write
Profile (par. 58.25)ABB Drives (or ABB Drives Enhanced)

If you plan to record status and reference words over time rather than just watch them, the embedded fieldbus adapter sits on the same shared RS-485 line as everything else in the cabinet. Modbus RTU data logger over RS-485 covers what one read costs at each baud rate and how to tell a wiring fault from a wrong node address.

// starting the drive

Control word sequence

The ABB Drives control word at 40001 needs a short bit sequence to bring the drive from stopped to running.

StepWrite to 40001Effect
10x0476Prepare: ready-on, no run yet
20x047FRun: drive accelerates to the reference
30x0476Stop (ramp down) — clears the run bit
Fault0x04F6, then 0x0476Fault reset: the stop word with bit 7 set, a rising edge of bit 7 (0x0480 would also clear OFF1–OFF3)

Important: the master must keep sending the control word and reference periodically (every 200–500 ms). With communication loss mode 58.15 at Cw / Ref1 / Ref2, only a write resets the timer, so a master that just keeps reading still lets it run out: when the writes stop and 58.14 is set to a fault, the ACS580 trips fault 6681 (communication loss) after 58.16. Check 58.14–58.16 on the drive. From ModbusManager Pro 1.9.10, the Motor / Drive faceplate does this for you: Write the command again every (ms) (500 ms in the ABB Drives preset) repeats the control word and the reference while the drive runs, and ends on Stop, Reset, a fault or a lost link.

// how to test it

Test an ACS580 in three steps

From wiring to a running drive without a PLC.

Step 1
Connect
Wire RS-485 A/B/ground to the drive’s EFB terminals. Set par. group 58 to Modbus RTU with a node address and baud rate, and set the command source to embedded fieldbus. In ModbusManager pick RTU with matching baud, parity and the drive’s slave address.
Step 2
Monitor
Read holding register 40004 (status word, address 3) and the mapped actual values from 40005 (address 4) to confirm communication. You should see the drive’s ready/running state and live feedback before you try to control it.
Step 3
Control & log
Write the control word sequence to 40001 (address 0) with a reference in 40002 (address 1) to start the drive, and keep writing them while it runs. Log feedback to the Historian, build a dashboard, or set alarms on overcurrent or faults.
// why modbusmanager

A practical tool for ABB drives

ModbusManager reads and writes any ACS580 register directly, with a serial monitor to see every frame. The Standard edition ($49) covers polling, writing and the serial monitor — enough to start, stop and monitor a drive. The Pro edition ($119) adds a drag-and-drop dashboard, a data logging Historian with CSV export, and an alarm system — all running locally on Windows, with no SCADA server or cloud account.

// frequently asked questions

ABB ACS580 Modbus — FAQ

What Modbus settings does an ABB ACS580 use?+
The ACS580 has an embedded fieldbus (EFB) that runs as a Modbus RTU slave on RS-485. Set the protocol to Modbus RTU in parameter group 58, choose a node address and baud rate (commonly 9600 or 19200), and match parity and stop bits in ModbusManager. The drive supports RTU only, not ASCII.
Which register is the ACS580 control word?+
In the ABB Drives profile the control word is Modbus holding register 40001, the frequency/speed reference is 40002, and the status word is 40004. These are the core registers for remote start, stop and speed control.
How do I start an ACS580 over Modbus?+
Set the command source to embedded fieldbus, then write the ABB Drives control word sequence to register 40001: typically 0x0476 then 0x047F to give the run command, together with a reference in 40002. The master must keep writing them periodically (every 200-500 ms) or the drive can trip on communication loss.
Why does the ACS580 not run when I write the control word?+
Common causes: the command source is not set to EFB, the control word bit sequence is incomplete, or the master is not transmitting continuously so the drive trips fault 6681 (communication loss). Send the control word and reference together periodically rather than as one-shot commands.
Can I monitor ACS580 speed and current with ModbusManager?+
Yes. Read the status word at 40004 and the actual values at 40005 and 40006 for output frequency and current. Power is not mapped by default: set 58.107 Data I/O 7 to 01.14 Output power and it appears at 40007. With ModbusManager Pro you can log them to the Historian, chart trends and set alarms on limits.
// several drives on one line

Many drives, one shared register map

A line with several ACS580 drives means several Modbus nodes for the PLC to address. ModbusManager Pro can collect the status word, actual speed and current of every drive into one register map — and forward speed references written by the PLC back to the correct drive. During commissioning this lets you prove the data mapping works before the PLC program is finished.

Modbus gateway software →
// other drives

Allen-Bradley drive on the same panel?

If the same line mixes ABB and Rockwell drives, the awkward part is not the register list but the addressing: PowerFlex documentation numbers registers in a way that lands one off on many Modbus masters. The PowerFlex 525 page explains why that happens and how to settle it on the drive itself.

PowerFlex 525 Modbus addressing →

Talk to your ABB drive in minutes

Download ModbusManager and connect to your ACS580 over RTU. Free 14-day Pro trial — no credit card, no cloud.

Download free trial See pricing

Windows 10/11 · Standard $49 · Pro $119 one-time