The ABB ACH580 HVAC drive has a Modbus RTU slave built in — the embedded fieldbus (EFB) on terminals 29–31. The register map is ABB's standard one, but the ACH580's HVAC defaults catch people out: the drive refuses to start until DI4 is closed, Actual value 2 reads zero until you configure it, and whether a lost BMS stops the fan depends on a parameter whose default changed between manual editions. This page covers the registers, the group 58 setup, the control word and those three traps, all from ABB's firmware manual.
The EFB is Modbus RTU only on RS-485 (the same port also speaks BACnet MS/TP and N2; 58.01 picks one). For Modbus TCP you need an option module (FMBT-21 or FENA-21) or a gateway. Wire 29 B+, 30 A- and 31 DGND on X5; the termination (S4) and bias (S5) switches are next to it — on only at the ends of the line.
| Parameter | Set to | Default / note |
|---|---|---|
| 58.01 Protocol enable | Modbus RTU | Off until you choose it |
| 58.03 Node address | 1–247 | 1 |
| 58.04 Baud rate | as the master | 19.2 kbps |
| 58.05 Parity | as the master | 8 EVEN 1 |
| 58.14 Communication loss action | Fault (or Speed ref safe) | No action in Rev J — see below |
| 58.15 Communication loss mode | — | Cw / Ref1 / Ref2: only writes reset the timer |
| 58.16 Communication loss time | — | 30.0 s |
| 58.25 Control profile | ABB Drives | ABB Drives (DCU Profile also possible) |
| 58.33 Addressing mode | Mode 0 | Mode 0 |
| 58.34 Word order | — | LO-HI (low word first) |
| 20.01 Ext1 commands | Embedded fieldbus | start / stop from Modbus |
| 28.11 Ext1 frequency ref1 | EFB ref1 | scalar control (the ACH580 default); 22.11 in vector |
| 58.06 Communication control | Refresh settings | group 58 changes take effect only after this or a reboot |
| 96.07 Parameter save manually | Save | keeps the values after power-off |
58.06 = Refresh settings or a power cycle. After power-up there is also a 30-second delay before the communication-loss supervision starts.
All registers are holding registers: read with FC03, written with FC06 or FC16. ABB numbers them 400001…; on the wire the address is that number minus 400001.
| ABB register | Wire | Default content | Selected by |
|---|---|---|---|
| 400001 | 0 | Control word (CW 16bit) | 58.101 |
| 400002 | 1 | Reference 1 (Ref1 16bit) | 58.102 |
| 400003 | 2 | Reference 2 (Ref2 16bit) | 58.103 |
| 400004 | 3 | Status word (SW 16bit) | 58.104 |
| 400005 | 4 | Actual value 1 (Act1 16bit) | 58.105 |
| 400006 | 5 | Actual value 2 (Act2 16bit) — 0 by default | 58.106 |
| 400007–400014 | 6–13 | Data I/O 7–14, None (read 0) until set | 58.107–58.114 |
| 400090–400095 | 89–94 | Error registers of the last query | — |
| 400101… | 100… | Any parameter, by 58.33 (next section) | — |
The ACH580 ships in scalar motor control (99.04), so with the default type Speed or frequency both Ref1 and Act1 are a frequency: 20000 = 46.02 Frequency scaling, which is 50.00 Hz or 60.00 Hz depending on the drive's 50/60 Hz setting. Act1 = 17966 on a 50 Hz drive is 17966 × 50 / 20000 = 44.9 Hz. In vector control they become speed, with 20000 = 46.01. Negative values (two's complement) mean reverse.
With 58.33 Addressing mode at its default Mode 0 every parameter has two addresses, so you do not have to map anything into Data I/O first:
| Parameter | 32-bit register | Wire | Scale (FbEq32) |
|---|---|---|---|
| 01.06 Output frequency | 420212 | 20211 | ÷ 100 → Hz |
| 01.07 Motor current | 420214 | 20213 | ÷ 100 → A |
| 01.10 Motor torque | 420220 | 20219 | ÷ 10 → % |
| 01.11 DC voltage | 420222 | 20221 | ÷ 100 → V |
| 01.13 Output voltage | 420226 | 20225 | V |
| 01.14 Output power | 420228 | 20227 | ÷ 100 → kW |
| 05.11 Inverter temperature | 421022 | 21021 | ÷ 10 → % of fault limit |
| Parameter | 16-bit register | Wire | Content |
|---|---|---|---|
| 04.01 Tripping fault | 400401 | 400 | Fault code (hex in the manual: 6681 = 0x6681) |
| 04.06 Active warning 1 | 400406 | 405 | Warning code, e.g. 0xAFEE |
| 10.02 DI delayed status | 401002 | 1001 | Bits 0–5 = DI1–DI6 |
ABB Drives profile, register 400001 (wire 0). Bit 10 REMOTE_CMD must be 1 for the drive to take commands from Modbus, which is why every value below has 0x400 in it. ABB's sequence for the ACH580:
| Step | Write to 400001 | Result |
|---|---|---|
| Start 1 | 1142 (0x0476) | NOT READY TO SWITCH ON |
| Start 2 | 1150 (0x047E) | READY TO SWITCH ON (stopped) — once SW bit 0 = 1 |
| Start 3 | 1151 (0x047F) | OPERATION (running) with the reference in 400002 |
| Stop | 1143 (0x0477) | Stop by 21.03 Stop mode — ABB's preferred stop |
| Ramp stop | 1150 (0x047E) | OFF1 ramp stop (cannot be interrupted) |
| Coast stop | 1149 (0x047D) | OFF2 emergency coast |
| Emergency ramp | 1147 (0x047B) | OFF3 emergency ramp stop |
| Fault reset | rising edge of bit 7 | e.g. 0x04F6, then back to 0x0476 |
The status word at 400004 (wire 3) answers: bit 0 ready to switch on, 1 ready to run, 2 running, 3 fault, 7 warning, 8 at setpoint, 9 remote. A running drive at speed under Modbus control reads 0x0337. The same bits are also readable one by one as discrete inputs (FC02, 100001…) and the control word bits as coils (FC01/FC05, 000001…); the digital inputs DI1–DI6 follow at 100033–100038.
The control word is right, the status word says ready, and nothing turns. On an ACH580 it is usually one of these, in this order:
The current firmware manual (3AXD50000027537 Rev J, 2026) lists 58.14 Communication loss action = No action as the default: if the master stops, the drive keeps running on the last command. Older editions of the same manual list Fault, so read 58.14 on the panel rather than trusting either. When it is Fault, the drive trips with 6681 EFB comm loss after 58.16 (30 s) — but only when control or the reference is expected from the EFB. Other choices: Last speed, Speed ref safe (22.41 / 28.41), Fault always, Warning (A7CE).
Mind 58.15: with the default Cw / Ref1 / Ref2 only a write of the control word or a reference resets the timer. A BMS that starts the fan once and then only reads will, with 58.14 = Fault, trip the drive 30 s later. Write the control word cyclically (ModbusManager's periodic write does this), or set 58.15 to Any message.
ABB ACH580 read-only monitor workspace. Open via Workspace › Open in ModbusManager Pro.
Faceplate, status bits, historian and alarms for your drives. Free 14-day trial. No credit card. Windows 10/11.
On BACnet instead? The ACH580 BACnet points list covers the same drive over MS/TP. For the general-purpose sibling see the ACS580 Modbus guide, and for references and scaling across brands the VFD speed reference guide.
Holding register 400004, which is address 3 on the wire (FC03). The control word is 400001 (address 0), the frequency reference 400002 (address 1) and Actual value 1 400005 (address 4).
Not on its own: the embedded fieldbus is Modbus RTU on RS-485. Modbus TCP needs an FMBT-21 or FENA-21 option module, or an RTU-to-TCP gateway.
By default 58.29 EFB act2 type is Transparent and 58.32 EFB act2 transparent source is Not selected, so register 400006 carries nothing. Set a source or read the parameter directly, e.g. 01.07 Motor current at 420214.
Most often the start interlock: in the HVAC default 20.41 Start interlock 1 is DI4, and with DI4 open the drive shows warning AFEE and does not start. Also check the panel is in Auto, 20.01 is Embedded fieldbus and bit 10 of the control word is set (0x047F, not 0x000F).
Reference 1 and Actual value 1 use 20000 = 46.02 Frequency scaling (50 or 60 Hz) in the default scalar control. Read 01.06 at 420212 in 32-bit instead and the value is simply Hz × 100.
ABB, ACH580 HVAC control program firmware manual, 3AXD50000027537 Rev J (2026-02-23): chapter "Modbus RTU control through the embedded fieldbus interface (EFB)" (pp. 287–313), parameter groups 01, 04, 05, 10, 20, 46, 58 and 99 (pp. 397–405, 477, 620–625), the additional parameter data (pp. 735–748) and the HVAC default I/O. Public download from the ABB library. The 58.14 default of Fault comes from the earlier Rev C (2017). Check the manual for your firmware version; the workspace was tested against a simulator built from this manual, not a physical drive.
An air handler has a supply fan, a return fan and pumps, each an ACH580 on the same RS-485 line. ModbusManager Pro can poll them all and republish status, frequency and current as one Modbus TCP map for the BMS or a PLC — one master on the line, many readers on the network.
Modbus gateway software →We use Google Analytics cookies to see how the site is used. You can accept or decline — declining keeps analytics off. See our Privacy Policy.