GoodWe's hybrid inverters — ET, EH, BT, BH and their relatives — publish a Modbus map that most integrations use without reading the first page. That page says the inverter answers on address 247, not 1. This guide covers the connection settings, the live-data block from 35100, the battery and BMS registers and a sign question the document leaves open, from GoodWe's own Modbus protocol for energy storage inverters.
| Setting | Value |
|---|---|
| Protocol | Modbus RTU on RS485 |
| Inverter address | 1–247, factory default 247 (0xF7) |
| Baud rate | 9600 (default) |
| Byte format | 1 start, 8 data, 1 stop — no parity (8N1) |
| Function codes | 03 read, 06 write single, 10h write multiple |
| Errors | 02 register address fault or too many registers, 03 data error, 04 verification error |
A master that polls address 1 gets silence and usually reports a timeout, not a wrong address — the most common reason a GoodWe "does not support Modbus". Values are integers sent high byte first; 32-bit values come in two registers, high word first.
FC03, addresses as listed. / 10 means divide the raw value by 10.
| Register | Value | Type | Scale |
|---|---|---|---|
| 35103 / 35104 | PV1 voltage / current | U16 | / 10 |
| 35105 | PV1 power | U32 | W |
| 35107–35109 | PV2 voltage, current, power | U16, U16, U32 | / 10, / 10, W |
| 35111–35117 | PV3, PV4 | as PV1 | |
| 35121 / 35122 / 35123 | Phase R inverter voltage / current / frequency | U16 | / 10, / 10, / 100 |
| 35124 | Phase R inverter power | S32 | W |
| 35126–35134 | Phases S and T, same layout | ||
| 35136 | Grid mode: 0 loss, 1 OK, 2 fault | U16 | — |
| 35137 | Total inverter power | S32 | W |
| 35139 | AC active power (meter power when the meter is connected) | S32 | W |
| 35171 | Total load power | S32 | W |
| 35174–35176 | Air / module / heatsink temperature | S16 | / 10 °C |
| 35180 / 35181 | Battery 1 voltage / current | U16 / S16 | / 10 |
| 35182 | Battery 1 power | S32 | W |
| 35184 | Battery 1 mode: 0 none, 1 standby, 2 discharging, 3 charging | U16 | — |
| 35187 | Work mode: 0 wait, 1 on-grid, 2 off-grid, 3 fault, 4 flash, 5 check | U16 | — |
| 35189 | Error message (bit field) | U32 | — |
| 35191 | PV energy total | U32 | / 10 kWh |
| 37007 | BMS state of charge | U16 | % |
Meter values sit from 36000: 36004 meter communication status (1 OK), 36005–36008 phase and total active power in 16 bits, and from ARM firmware above version 9 the 32-bit set from 36019, with total active power at 36025.
GoodWe's protocol gives battery power (35182) and meter power as signed numbers, but it does not say which sign means charging or exporting. Do not guess from one reading: 35184 Battery Mode says it in words — 2 discharging, 3 charging — and grid power can be calculated from the balance, load − PV − battery discharge. The workspace's script does both, so the flow diagram is right whatever sign your firmware uses.
GoodWe ET hybrid workspace (address 247). Open via Workspace › Open in ModbusManager Pro.
Energy-flow element, historian and MQTT to Home Assistant. Free 14-day trial. No credit card. Windows 10/11.
Other hybrids: Deye / Sunsynk / Growatt, Victron Cerbo GX, Huawei SUN2000, Sungrow.
247 (0xF7). GoodWe's protocol allows 1 to 247 and ships with 247, so a master polling address 1 gets no answer. The default baud rate is 9600, 8 data bits, no parity, 1 stop bit.
PV1 power is 35105 (U32, W), PV2 35109, PV3 35113, PV4 35117. Voltages are at 35103, 35107 and so on, divided by 10.
Register 37007 holds the BMS state of charge in percent. Battery voltage is 35180 (/10), current 35181 (/10), power 35182 and the charge / discharge state 35184.
The protocol does not say. Use Battery1 Mode 35184 for the direction (2 discharging, 3 charging) and the magnitude of 35182 for the power.
FC03 to read, FC06 to write a single register and FC10 (16) to write several. 32-bit values come high word first.
GoodWe, GoodWe Modbus Protocol Hybrid — For Energy Storage Inverters, version 1.2 (2024-02-02), published on goodwe.com as the third-party EMS protocol. Register sets differ between hybrid families and firmware (the meter block changed at ARM version 9); check the map for your model. Tested against a simulator built from this document, not a physical inverter.