GoodWe's hybrid inverters — ET, EH, BT, BH and their relatives — publish a Modbus map that most integrations use without reading the first page. That page says the inverter answers on address 247, not 1. This guide covers the connection settings, the live-data block from 35100, the battery and BMS registers and a sign question the document leaves open, from GoodWe's own Modbus protocol for energy storage inverters.

ModbusManager Pro dashboard for a GoodWe ET hybrid inverter on address 247: energy flow with 5.4 kW solar, battery at 64 % charging with 1.7 kW, 2.0 kW house load and 1.7 kW export; PV string voltages, grid status OK, work mode on-grid, battery mode charging, battery voltage, current and SOC, phase voltage, heatsink temperature, total PV energy and a trend of PV, load and grid power
The free workspace below on a simulated ET inverter — FC03 at address 247, registers from 35103.

Connection Settings

SettingValue
ProtocolModbus RTU on RS485
Inverter address1–247, factory default 247 (0xF7)
Baud rate9600 (default)
Byte format1 start, 8 data, 1 stop — no parity (8N1)
Function codes03 read, 06 write single, 10h write multiple
Errors02 register address fault or too many registers, 03 data error, 04 verification error

A master that polls address 1 gets silence and usually reports a timeout, not a wrong address — the most common reason a GoodWe "does not support Modbus". Values are integers sent high byte first; 32-bit values come in two registers, high word first.

Live Data from 35100

FC03, addresses as listed. / 10 means divide the raw value by 10.

RegisterValueTypeScale
35103 / 35104PV1 voltage / currentU16/ 10
35105PV1 powerU32W
35107–35109PV2 voltage, current, powerU16, U16, U32/ 10, / 10, W
35111–35117PV3, PV4as PV1
35121 / 35122 / 35123Phase R inverter voltage / current / frequencyU16/ 10, / 10, / 100
35124Phase R inverter powerS32W
35126–35134Phases S and T, same layout
35136Grid mode: 0 loss, 1 OK, 2 faultU16—
35137Total inverter powerS32W
35139AC active power (meter power when the meter is connected)S32W
35171Total load powerS32W
35174–35176Air / module / heatsink temperatureS16/ 10 °C
35180 / 35181Battery 1 voltage / currentU16 / S16/ 10
35182Battery 1 powerS32W
35184Battery 1 mode: 0 none, 1 standby, 2 discharging, 3 chargingU16—
35187Work mode: 0 wait, 1 on-grid, 2 off-grid, 3 fault, 4 flash, 5 checkU16—
35189Error message (bit field)U32—
35191PV energy totalU32/ 10 kWh
37007BMS state of chargeU16%

Meter values sit from 36000: 36004 meter communication status (1 OK), 36005–36008 phase and total active power in 16 bits, and from ARM firmware above version 9 the 32-bit set from 36019, with total active power at 36025.

Which Way Does the Power Flow?

GoodWe's protocol gives battery power (35182) and meter power as signed numbers, but it does not say which sign means charging or exporting. Do not guess from one reading: 35184 Battery Mode says it in words — 2 discharging, 3 charging — and grid power can be calculated from the balance, load − PV − battery discharge. The workspace's script does both, so the flow diagram is right whatever sign your firmware uses.

Common Mistakes

Step-by-Step: Reading a GoodWe ET with ModbusManager

  1. Wire a USB–RS485 adapter to the inverter's RS485 / COM port (or use a Modbus TCP gateway).
  2. In ModbusManager choose RTU, 9600, no parity, 1 stop bit, unit 247.
  3. Poll FC03 from 35103, quantity 8: PV1 and PV2 voltage, current and power.
  4. Open the workspace below for the energy flow and all values scaled.

Download a Ready-Made Workspace

Read-only. Nothing is written. Unit ID 247. Tags, script and dashboard are ModbusManager Pro features; Standard opens the poll windows only.

GoodWe_ET_Hybrid.json

GoodWe ET hybrid workspace (address 247). Open via Workspace › Open in ModbusManager Pro.

Download Workspace

Try it with ModbusManager Pro

Energy-flow element, historian and MQTT to Home Assistant. Free 14-day trial. No credit card. Windows 10/11.

Download Pro Trial

Other hybrids: Deye / Sunsynk / Growatt, Victron Cerbo GX, Huawei SUN2000, Sungrow.

Frequently Asked Questions

What is the default Modbus address of a GoodWe inverter?

247 (0xF7). GoodWe's protocol allows 1 to 247 and ships with 247, so a master polling address 1 gets no answer. The default baud rate is 9600, 8 data bits, no parity, 1 stop bit.

Where is PV power in the GoodWe Modbus map?

PV1 power is 35105 (U32, W), PV2 35109, PV3 35113, PV4 35117. Voltages are at 35103, 35107 and so on, divided by 10.

How do I read the GoodWe battery state of charge?

Register 37007 holds the BMS state of charge in percent. Battery voltage is 35180 (/10), current 35181 (/10), power 35182 and the charge / discharge state 35184.

Is GoodWe battery power positive when charging?

The protocol does not say. Use Battery1 Mode 35184 for the direction (2 discharging, 3 charging) and the magnitude of 35182 for the power.

Which function code does GoodWe use?

FC03 to read, FC06 to write a single register and FC10 (16) to write several. 32-bit values come high word first.

Sources

GoodWe, GoodWe Modbus Protocol Hybrid — For Energy Storage Inverters, version 1.2 (2024-02-02), published on goodwe.com as the third-party EMS protocol. Register sets differ between hybrid families and firmware (the meter block changed at ARM version 9); check the map for your model. Tested against a simulator built from this document, not a physical inverter.