Every device. One tool. Pay once. Modbus · BACnet · Siemens S7 · one-time licence · also from us: BACManager ↗

Danfoss AK-CC 350 Modbus: Parameter Numbers Minus One, Case Temperatures and Alarm Bits

The Danfoss AK-CC 350 controls a refrigerated display case or a small cold room — compressor or liquid-line valve, defrost, fan, alarm and light relays — and has Modbus RTU built in. Danfoss publishes its full Modbus parameter list. This guide covers the parameter-number addressing, the temperatures (which the list calls “Float” but are not), the controller state, the alarm bits, and the one thing Danfoss leaves out for this model: the serial settings.

ModbusManager Pro dashboard for a Danfoss AK-CC 350 on a dairy case: air 2.4 °C at cutout 2.0 °C, compressor off, no defrost, EKC state stopped by thermostat, main switch start, S3 3.4 °C, S4 1.3 °C, evaporator -2.0 °C, all alarms OK, fan running, and a trend of air, cutout and evaporator temperature through compressor cycles
The free workspace below on a simulated AK-CC 350 — the compressor cycling on the thermostat, the evaporator following.

Connection

PNU X Is Wire Address X − 1

Danfoss lists every value by its parameter number (PNU), and its Modbus design guide says the register number is the PNU, sent as PNU − 1: the air temperature u17 is PNU 2532, on the wire 2531; the main switch r12 is PNU 117, address 116. Read the PNU itself and you get the neighbouring parameter.

Key Parameters

CodePNUValueScale
u172532Thermostat air temperature0.1 °C
u562576Display air temperature0.1 °C
u12 / u162530 / 2531S3 air in / S4 air out0.1 °C
u091011S5 evaporator (defrost sensor)0.1 °C
r00100“Cutout °C” — the set point (read / write, −50.0…50.0)0.1 °C
u282546Actual temperature reference (with night offset)0.1 °C
u002007EKC State (table below)—
1036Defrost state 0 / 1—
1013Defrost start (write 1)—
r12117Main switch: 1 start, 0 stop, −1 manual control of outputs—
u58 / u59 / u60 / u622510 / 2511 / 2512 / 2583Relays: compressor or LLSV, fan, defrost, alarm0 / 1
A13 / A1410019 / 10020High / low alarm limit0.1 °C

“Float” is not a float. The list types the temperatures as Float, but each is one signed 16-bit register in tenths of a degree: its range −2000…2000 is the user guide's −200.0…200.0 °C. −30.0 °C arrives as 0xFED4 = −300. Read two registers as an IEEE float and you get nonsense.

EKC State (u00, PNU 2007)

CodeStateCodeState
0Regulating14Defrost
1Waiting for end of coordinated defrost15Fan delay after defrost
2 / 3Min ON / min OFF time17Door open
4Drip-off20Emergency cooling
10Stopped by main switch25Manual control
11Stopped by thermostat29Case cleaning

Alarm Bits

One register per alarm, 0 or 1, from PNU 20000: 20000 EKC error, 20002–20004 S3 / S4 / S5 sensor error, 20005 high temperature, 20006 low temperature, 20007 HACCP, 20008 door, 20009 / 20010 DI1 / DI2, 20011 max defrost time, 20012 max hold time, 20013 case cleaning, 20014 standby. These numbers are the AK-CC 350's: the AK-CC55 Compact puts high temperature at 20007 and door at 20009. Never copy an alarm map between models.

Common Mistakes

Step-by-Step: Reading an AK-CC 350 with ModbusManager

  1. Set o03 to the controller's address.
  2. In ModbusManager choose RTU, 38400, even parity, 1 stop bit (then 19200 / 9600 if it does not answer).
  3. Read FC03 from address 2529, quantity 3: S3, S4 and the air temperature u17, × 0.1.
  4. Read 2006 for the EKC state and 19999, quantity 15, for the alarm bits. Or open the workspace below.

Download a Ready-Made Workspace

Read-only. Nothing is written — no cutout, no main switch, no defrost. Address 1; the baud rate and parity are yours to set (see Connection). Tags and dashboard are ModbusManager Pro features; Standard opens the poll windows only.

Danfoss_AKCC350.json

Danfoss AK-CC 350 case controller workspace (Modbus RTU). Open via Workspace › Open in ModbusManager Pro, or from the in-app Device library.

Download Workspace

Try it with ModbusManager Pro

Display-case and cold-room elements, HACCP-style historian, alarms on case temperature, and MQTT to Home Assistant. Free 14-day trial. No credit card. Windows 10/11.

Download Pro Trial

Temperature control on a process line: Omron E5CC. Drives on the same site: Danfoss VLT FC 102 / FC 302. All guides: Modbus device guides.

Frequently Asked Questions

What are the Modbus settings of a Danfoss AK-CC 350?

The address is parameter o03 (1-240, 0 = off). Danfoss' AK-CC 350 documents do not state the baud rate or parity; Danfoss' AK-SM 800A uses 38400 8E1 on its Danfoss channel, so start there, then try 19200 and 9600.

How do I convert a Danfoss PNU to a Modbus address?

Subtract one: PNU 2532 (air temperature u17) is wire address 2531, PNU 117 (main switch r12) is 116. In 4xxxx notation PNU 2532 is 42532.

Why does the AK-CC 350 temperature read as nonsense when read as a float?

The parameter list calls it Float, but each temperature is one signed 16-bit register in tenths of a degree: 24 is 2.4 °C, -300 is -30.0 °C.

Where is the set point of an AK-CC 350?

Parameter r00, "Cutout °C", PNU 100 (wire 99), signed 0.1 °C, -50.0 to 50.0. The actual reference with night offset is u28, PNU 2546.

Which register shows defrost on an AK-CC 350?

Defrost state, PNU 1036 (0/1), and EKC State PNU 2007 = 14 during defrost. The defrost relay u60 is PNU 2512.

Sources

Danfoss, Programming guide — Modbus parameter list, AK-CC 350, SW 1.1x, AU451945704197en-000101 (2023.05); User guide AK-CC 350, RS8EQ302 (2015-12); Data communication Modbus RS485 RTU design guide, AJ260040756410en-000101 (2015.10), all assets.danfoss.com. The serial settings come from Danfoss' AK-SM 800A and AK-CC55 documents, not the AK-CC 350's. Tested against a simulator built from these documents, not against a physical controller.

// beyond the case

The cases plus the rest of the store

ModbusManager Pro reads every case controller on the line next to the rack, meters and HVAC, and republishes the values as one Modbus TCP map or as MQTT topics with Home Assistant discovery.

Modbus gateway software →