The Socomec DIRIS A-40 is a panel-mounted multifunction meter and power analyser — RS-485 (48250500) or with an Ethernet gateway (48250501). Its Modbus table holds the same measurements twice: a legacy block at 50512 that older DIRIS integrations use, and a newer layout from 18432 and 36864. They are not scaled the same way, and mixing them is the classic DIRIS mistake. This guide covers both, plus the THD and individual harmonic registers.
All two-register values. One FC03 read of 62 registers from 50512 gets everything below.
| Address | Value | Type | Unit |
|---|---|---|---|
| 50512 | Hour meter | U32 | h / 100 |
| 50514 / 16 / 18 | U12 / U23 / U31 | U32 | V / 100 |
| 50520 / 22 / 24 | V1 / V2 / V3 | U32 | V / 100 |
| 50526 | Frequency | U32 | Hz / 100 |
| 50528 / 30 / 32 | I1 / I2 / I3 | U32 | mA |
| 50534 | Neutral current | U32 | mA |
| 50536 | Total active power | S32 | 10 W |
| 50538 / 50540 | Total reactive / apparent power | S32 / U32 | 10 var / 10 VA |
| 50542 | Total power factor (− leading, + lagging) | S32 | / 1000 |
| 50544–50548 | P1 / P2 / P3 | S32 | 10 W |
| 50562–50566 | PF1 / PF2 / PF3 | S32 | / 1000 |
| 50780 | Partial (resettable) active energy + | U32 | kWh |
| Address | Value | Type | Unit |
|---|---|---|---|
| 36871 | Frequency | U32 | mHz |
| 36873… | V1 / V2 / V3 | U32 | V / 100 |
| 18458… | I1 / I2 / I3 / In | U32 | mA |
| 18476 | Total active power | S32 | W |
| 18486 / 18487 | Total PF / PF type (1 leading, 2 lagging) | S16 / U16 | / 1000 |
| 19843 + 19845 | Total active energy imported: kWh + residual | U32 + U16 | kWh + 0.1 Wh |
| 19846 + 19848 | Total active energy exported | U32 + U16 | kWh + 0.1 Wh |
The same 52.7 kW reads as 5270 at 50536 and 52 700 at 18476. Pick one map and scale it for that map.
| Address | Value | Type | Unit |
|---|---|---|---|
| 37144 / 45 / 46 | THD V1 / V2 / V3 | U16 | % / 100 |
| 37147 / 48 / 49 | THD U12 / U23 / U31 | U16 | % / 100 |
| 18757 / 58 / 59 / 60 | THD I1 / I2 / I3 / In | U16 | % / 100 |
| 18767 | System THD I | U16 | % / 100 |
| 37504… | Voltage harmonics: rank 2 V1, V2, V3, then rank 3 … | U16 | % / 100 |
| 19713… | Current harmonics: rank 2 I1, I2, I3, In, then rank 3 … | U16 | % / 100 |
THD of voltage lives in the network range (371xx), THD of current in the load range (187xx). A value of 1420 is 14.20 %. Register 34819 says whether THD is referred to the fundamental (0) or to the RMS value (1).
Socomec DIRIS A-40 workspace (legacy block, THD, energy). Open via Workspace › Open in ModbusManager Pro, or from the in-app Device library.
Three-phase meter element, alarms on THD and unbalance, historian, and MQTT to Home Assistant. Free 14-day trial. No credit card. Windows 10/11.
Other power analysers on this site: Janitza UMG 96-PA, Schneider PM5000, Carlo Gavazzi EM340. All of them: Modbus device guides.
Legacy 50512 block: 50536, signed 32-bit in 10 W (5270 = 52.7 kW). Newer layout: 18476, signed 32-bit in W. Both are read with FC03, address as listed.
You are reading 36871 in the newer layout, which is in mHz. The legacy register 50526 gives the frequency in Hz / 100 (4999).
THD of voltage at 37144–37151 (V1–V3, U12–U31, system), THD of current at 18757–18760 (I1–I3, In) and 18767 (system), all U16 in % / 100. Individual harmonics start at 37504 (voltage) and 19713 (current).
No. Socomec's table lists only integers (U16, S16, U32, S32, U64). Register lists with floats belong to other devices or other generations.
Socomec's Modbus table does not state factory defaults. They are set in the meter's menu and can be read back at 57344 (address), 57345 (baud), 57346 (stop bits) and 57347 (parity).
Socomec, MODBUS tables of DIRIS A-40, V 174.403 (socomec.fr). Word order of 32-bit values and the factory serial settings are not stated in it. Tested against a simulator built from this table, not against a physical meter.