Every device. One tool. Pay once. Modbus · BACnet · Siemens S7 · one-time licence · also from us: BACManager ↗

Grundfos MAGNA3 Modbus (CIM 200 / CIM 500): Registers Minus One, Remote Access and the Setpoint in Percent

A Grundfos MAGNA3 circulator — like the CRE, TPE and other E-pumps — speaks Modbus through a CIM module: CIM 200 for Modbus RTU on RS-485, CIM 500 for Modbus TCP. Grundfos publishes one functional profile for all of them. It is clear once you know three things: register numbers go on the wire minus one, the pump ignores commands until the bus asks for remote access, and the setpoint is a percentage of a range, not a head in metres.

ModbusManager Pro dashboard for a Grundfos MAGNA3 on a CIM 200: pump running with flow 9.0 m³/h, head 0.40 bar and 65 % performance, control mode AUTOADAPT, local control, 3116 rpm, 179 W, liquid 61.3 °C, setpoint 42 %, 20 Wh/m³, 2843 kWh, no alarm, 18450 hours, 412 starts, and a flow and head trend
The free workspace below on a simulated MAGNA3 with a CIM 200 — Modbus RTU 19200 8E1, two block reads.

CIM 200 and CIM 500 Settings

CIM 200 (Modbus RTU)CIM 500 (Modbus TCP)
Address1–247 on two hex rotary switches (SW6 high, SW7 low)Unit ID not used
SpeedDIP SW4/SW5: 19200 default, 9600, 38400 or software-defined—
FramingSW3: even parity, 1 stop bit default; ON = no parity, 2 stop—
WiringD1+, D0− and Common; termination SW1+SW2, off by defaultEthernet
First step—Protocol switch to position 1 = Modbus TCP — the factory setting 0 is PROFINET. Set the Modbus TCP address in the web server (default 192.168.1.100); it must differ from the web server's own.

Function codes 03, 04, 06, 16 and 08 — no coils. FC03 and FC04 return the same data. One request reads at most 125 registers.

Register X Is Wire Address X − 1

Grundfos numbers its registers 00001, 00101, 00201… and says it in the profile: registers numbered X are addressed as X − 1. The setpoint 00104 goes on the wire as 103, the status word 00201 as 200. Values over 65 535 use two registers, high then low.

Key Registers

RegisterValueScale
00101Control bits: 0 RemoteAccessReq, 1 OnOffReq, 2 ResetAlarm (rising edge)bits
00102Control mode: 0 const. speed, 3 const. head, 5 const. diff. pressure, 6 proportional pressure, 7 const. flow, 128 AUTOADAPT, 129 FLOWADAPT—
00103Operation mode: 0 auto, 4 min, 6 max—
00104Setpoint, % of the setpoint range (0–10000)0.01 %
00201Status bits: 6 rotation, 8 remote access, 9 on, 10 alarm, 11 warning, 13 at max speed, 15 at min speedbits
00202Process feedback0.01 %
00205 / 00206Alarm code / warning code (0 = none)—
00209–00211Feedback sensor unit, min, max—
00215 / 00216Setpoint range min / max, % of sensor max0.01 %
00301Head0.001 bar
00302Volume flow (estimated, for monitoring only)0.1 m³/h
00303 / 00304Relative performance / speed0.01 % / rpm
00308Actual setpoint0.01 %
00312–00313Power (U32, high then low)W
00322Pumped liquid temperature0.01 K
00326Specific energyWh/m³
00327–00328 / 00332–00333 / 00334–00335Operating hours / energy / starts (U32)h / kWh / —

“A data value of 0xFFFF indicates not available” — the profile has a MAGNA3 column, and registers such as motor voltage or torque are not available on it. Temperatures are given in 0.01 K with no offset stated; the workspace reads them as absolute kelvin (− 273.15), so check the first reading against the pump's display.

Remote Access and the Setpoint

Common Mistakes

Step-by-Step: Reading a MAGNA3 with ModbusManager

  1. Set the CIM 200 address on the rotary switches (or put the CIM 500 on position 1).
  2. In ModbusManager choose RTU, 19200, even parity, 1 stop bit, that address — or TCP for the CIM 500.
  3. Read FC03 from address 200, quantity 26: the status block 00201–00226.
  4. Read FC03 from address 300, quantity 36: head, flow, speed, power, temperatures, energy. Or open the workspace below.

Download a Ready-Made Workspace

Read-only. Nothing is written — no remote access, no setpoint. The polls use slave address 1, 19200 8E1; for a CIM 500 choose TCP (the unit ID is ignored). Tags, script and dashboard are ModbusManager Pro features; Standard opens the poll windows only.

Grundfos_MAGNA3_CIM.json

Grundfos MAGNA3 workspace (CIM 200 / CIM 500). Open via Workspace › Open in ModbusManager Pro, or from the in-app Device library.

Download Workspace

Try it with ModbusManager Pro

Pump element with fault state, alarms on Grundfos alarm codes, historian, and MQTT to Home Assistant. Free 14-day trial. No credit card. Windows 10/11.

Download Pro Trial

The same pump over BACnet: Grundfos CIM on BACnet (bacmanager.com). Heat source next to it: NIBE S-series heat pumps. All guides: Modbus device guides.

Frequently Asked Questions

What are the default Modbus settings of a Grundfos CIM 200?

19200 baud, even parity, 1 stop bit, set with DIP switches; the address (1–247) is set on two hex rotary switches. A CIM 500 must be switched to position 1 for Modbus TCP, and it ignores the unit ID.

Why are my Grundfos Modbus values one register off?

Grundfos register X is addressed as X − 1: status 00201 is wire address 200, the setpoint 00104 is 103. A tool that adds 1 itself needs the number as written.

Why does the MAGNA3 ignore my setpoint over Modbus?

The bus must first take control: set bit 0 (RemoteAccessReq) of register 00101. Status bit 8 of 00201 shows remote access. The setpoint 00104 is then a percentage (0.01 %) of the setpoint range, not a head in metres.

What does 65535 mean in a Grundfos register?

Not available. The functional profile lists which registers each pump family has; a MAGNA3 has no motor voltage or torque, for example.

Is the MAGNA3 flow reading accurate?

It is estimated from the pump's operating point. Grundfos says to use it for monitoring only.

Sources

Grundfos, Modbus for Grundfos pumps — SoftCIM, CIM/CIU 200 Modbus RTU, CIM/CIU 500 Ethernet for Modbus TCP, functional profile and user manual, 98367081 05.2025 (api.grundfos.com, literature 6012947). The kelvin offset of the 0.01 K temperatures is not stated in it. Tested against a simulator built from this document, not against a physical pump.

// beyond the pump

The pump plus the rest of the plant room

ModbusManager Pro reads the circulator next to the heat source, meters and valves, and republishes the values as one Modbus TCP map or as MQTT topics with Home Assistant discovery.

Modbus gateway software →