Every device. One tool. Pay once. Modbus · BACnet · Siemens S7 · one-time licence · also from us: BACManager ↗

Schneider PM3250 / PM3255 Modbus Register Map (PM3200 Series)

How to read a Schneider Electric PM3200-series DIN-rail power meter over Modbus RTU. Only two of the four models have Modbus at all, the documented register is one more than the address on the wire, the meter knows FC03 and FC16 only, and energy comes twice — as an exact 64-bit integer and as a 32-bit float that quietly loses precision on a big feeder. This page covers all of it, from Schneider's current user manual.

ModbusManager Pro dashboard for a Schneider PM3255 on a low-voltage feeder: three-phase meter with phase voltages, currents and powers, active energy import read as Int64 and as Float32 side by side, power factor decoded from the four-quadrant register, neutral current, reactive and apparent power, meter temperature, tan phi, frequency and a power and current trend
The free workspace below on a simulated PM3255 with the register map on this page — note the last digits of the two energy values.

Which PM3200 Models Have Modbus

ModelModbusOther I/O
PM3200nodisplay only
PM3210nopulse output
PM3250RS-485, Modbus RTU—
PM3255RS-485, Modbus RTU2 digital inputs, 2 digital outputs, demand and energy logs

All four measure through CTs (1 A or 5 A secondaries) and optionally VTs. If the front says PM3200 or PM3210, no Modbus setting will make it answer — it has no port.

Connection Settings

SettingValuesNotes
TerminalsD0 (A / Rx-, Tx-), D1 (B / Rx+, Tx+), 0 VTwo-wire RS-485, one port, 4 kV isolated
Baud rate9600, 19200, 38400Set on the meter's display
ParityEven, Odd, NoneAlways 1 stop bit — with None that is 8N1, not 8N2
Address1–247Set on the display
Function codes03, 16, 43/14, 20Read holding, write multiple, device identification, read file record (logs)
No FC04, no FC06. Everything is a holding register read with FC03; an input-register read (FC04) is refused. A write of even one register must be FC16 with a quantity of 1 — masters that default to FC06 for single writes get an error. The yellow LED flashes while the meter communicates (also on a line error) and is off when nothing talks to it.

Register = Address + 1

Schneider's register tables give both numbers, and the manual states the rule outright: the address (hex) is what goes in the Modbus frame, and register = address + 1. Phase-1 current is register 3000 at address 0x0BB7 = 2999. A tool that takes 0-based addresses wants 2999; one with 1-based addressing wants 3000. Ask a 0-based tool for 3000 and every Float32 comes back as half of one value and half of the next.

The values are IEEE-754 Float32 in two registers. The manual does not spell out the word order; on this meter, as on other Schneider meters, the high word comes first — a phase voltage reading near 230 confirms it, a value like 1.2e-38 means the words are swapped.

Measurement Registers

All FC03, Float32 (two registers) unless noted. Wire is the 0-based address.

RegisterWireValueUnit
3000 / 3002 / 30042999 / 3001 / 3003Current I1 / I2 / I3A
30063005Neutral current InA
30103009Current averageA
3020 / 3022 / 30243019 / 3021 / 3023Voltage L1-L2 / L2-L3 / L3-L1V
3028 / 3030 / 30323027 / 3029 / 3031Voltage L1-N / L2-N / L3-NV
3054 / 3056 / 30583053 / 3055 / 3057Active power phase 1 / 2 / 3kW
30603059Total active powerkW
30683067Total reactive powerkVAR
30763075Total apparent powerkVA
3078–30843077–3083Power factor phase 1–3, total (−2…+2 format)—
31083107Tan phi (reactive factor)—
31103109FrequencyHz
31323131Meter temperature°C
3012–3018, 3038–30523011–, 3037–Current and voltage unbalance%
3766 / 37703765 / 3769Active power present / peak demandkW
Read in gap-free blocks. The list has holes (3008, 3034, 3086–3107…), and the manual does not say what the meter answers for a register that is not listed. The workspace below polls only runs of documented registers: 3000–3007, 3010–3033, 3036–3085, 3108–3111.

Power Factor: the −2 to +2 Register

Registers 3078–3084 do not hold a plain power factor. Schneider encodes the quadrant into the number: between 0 and +1 is Q1 (active power positive, inductive), between +1 and +2 is Q4 (positive, capacitive), between −1 and 0 is Q3 and between −2 and −1 is Q2 (active power negative). A reading of 1.08 is a 0.92 capacitive power factor: PF = 2 − 1.08. Below −1 it is −2 − x. Show the raw register on an HMI and a perfectly good 0.92 leading load looks like an impossible 1.08.

Energy: Int64 or Float32

The PM3200 gives every energy counter twice, both in Wh (not kWh):

CounterInt64 register (4 words)Float32 register
Active energy import320445166
Active energy export320845168
Reactive import / export3220 / 322445170 / 45172
Apparent import / export3236 / 324045174 / 45176
Partial active import325645178
Tariff 1–4 active import4196 / 4200 / 4204 / 420845206–45212

The Int64 value is exact. The Float32 has a 24-bit mantissa, so above 224 Wh — 16.8 MWh, a few months on a busy feeder — it can no longer count single watt-hours, and the step grows as the counter does: 2 Wh steps from 16.8 MWh, 4 Wh from 33.6 MWh, 64 Wh around a gigawatt-hour. For billing or sub-metering read the Int64. ModbusManager has no 64-bit data type, so the workspace reads the four words as UInt16 and combines them in its script: ((w0 × 65536 + w1) × 65536 + w2) × 65536 + w3.

Writing: the Command Interface

Settings are not written into their own registers. The meter has a command interface: write the command number to 5250 and its parameters from 5252 with one FC16, then read the result at 5376 (0 = valid; 3000 invalid command, 3001 invalid parameter, 3002 wrong number of parameters, 3007 not performed). Examples from the manual: 1003 sets date and time, 2060 selects the multi-tariff mode (1 = controlled over communication), 2008 sets the active tariff 1–4 — only when the tariff is under communication control. The active tariff can be read at 4191. Wiring, CT and VT ratios are set on the display; they are not in the Modbus list.

PM3255 Extras

Common Mistakes

Step-by-Step: Reading a PM3250 with ModbusManager

  1. On the meter's display set the address, baud rate and parity (one stop bit is fixed).
  2. Wire a USB–RS-485 adapter to D0, D1 and 0 V; terminate the line at both ends.
  3. In ModbusManager choose RTU, the COM port and the same baud rate and parity.
  4. Poll FC03 from address 2999, quantity 8, as Float32: I1, I2, I3 and In in amps.
  5. Open the workspace below to get all values named and scaled, the power factor decoded and the exact energy counter.

Download a Ready-Made Workspace

Read-only, PM3250 and PM3255. Nothing is written. Unit ID 1; change it in the polls and tags for another address. Tags, script and dashboard are ModbusManager Pro features; Standard opens the poll windows only.

SchneiderPM3200_workspace.json

Schneider PM3250 / PM3255 workspace. Open via Workspace › Open in ModbusManager Pro.

Download Workspace

Try it with ModbusManager Pro

Scaled tags, three-phase meter, historian and energy reports for your meters. Free 14-day trial. No credit card. Windows 10/11.

Download Pro Trial

The panel-mount PowerLogic PM5100 / PM5300 uses the same measurement registers — see the PM5000 Modbus guide. Eastron meters work differently (input registers, FC04): SDM630.

Frequently Asked Questions

Does the Schneider PM3200 have Modbus?

Only the PM3250 and PM3255 do, on RS-485 (Modbus RTU). The PM3200 and PM3210 have no communication port; the PM3210 has a pulse output.

What is the Modbus address of the PM3250 total active power?

Register 3060, which is address 3059 on the wire (FC03, Float32, kW). Schneider's rule is register = address + 1, so phase-1 current, register 3000, is address 2999.

Why does the PM3250 power factor read more than 1?

Registers 3078–3084 use a four-quadrant format from −2 to +2. A value between 1 and 2 is a capacitive power factor of 2 minus the value: 1.08 means 0.92 leading.

Should I read PM3200 energy as Int64 or Float32?

Int64 at 3204 for anything you bill or compare. Both are in Wh, but the Float32 copy at 45166 stops resolving single watt-hours above 16.8 MWh.

Why does my master get "illegal function" from the PM3250?

The meter supports FC03, FC16, 43/14 and 20 only. FC04 reads and FC06 single-register writes are refused; use FC03 to read and FC16 with a quantity of 1 to write one register.

Sources

Schneider Electric, PM3200 series – User manual, DOCA0006EN-09 (07/2026): main characteristics (pp. 13–14), wiring (p. 23), Modbus communication and register list (pp. 49–67), power factor register format (pp. 80–81), specifications (p. 87). Public download from se.com. The word order of the 32- and 64-bit values is not stated in the manual; the high-word-first order used here is the one Schneider meters use. The workspace was tested against a simulator built from this manual, not a physical meter.

// one panel, many meters

Every sub-meter in one map

A distribution board often has a dozen PM3250s on one RS-485 line. ModbusManager Pro can poll them all, decode the power factor and the Int64 energy once, and republish clean values as one Modbus TCP map for the BMS, an EMS or a PLC — or send them to MQTT.

Modbus gateway software →