Every device. One tool. Pay once. Modbus · BACnet · Siemens S7 · one-time licence · also from us: BACManager ↗

Omron E5CC Modbus RTU: Switch from CompoWay/F, Two Address Maps, No Decimal Point

Omron's E5CC and E5EC (the E5□C family) temperature controllers have RS-485 and speak Modbus RTU — but not out of the box. They ship set to Omron's own CompoWay/F protocol, they hold every value in two address maps at once, and they send integers with the decimal point left out. This guide covers the switch, the registers a dashboard needs, and how to read the status bits, including the one that says 1 when the controller is stopped.

ModbusManager Pro dashboard for an Omron E5CC: PID loop faceplate with PV 150.0 °C at set point 150.0 °C and output 40 % after a set point step from 120 °C, RUN, alarm 1 OK, heater current 8.2 A, alarm value 5.0, sensor OK, decimal point 1, auto mode, and a trend of PV, SP and MV
The free workspace below on a simulated E5CC — a set point step from 120 to 150 °C, the 2-byte map from 0x2000.

Switch the Protocol to Modbus

In the communications setting level (hold the O key 3 s for the initial setting level, then press it under 1 s), set:

ParameterFactoryFor Modbus
PSELCompoWay/F (cwf)Modbus (mod)
U-NO1slave address 1–99
BPS9.69600 / 19200 / 38400 / 57600
PRTYeveneven or odd with 1 stop bit, or none with 2 stop bits (8 data bits)
SDWT20 mssend data wait time

Then reset the controller — Omron's manual: new communications settings are enabled by resetting. Until then it still answers in CompoWay/F and a Modbus master sees nothing.

Two Maps for the Same Values

Omron's own example: PV in 4-byte mode 01 03 00 00 00 02, in 2-byte mode 01 03 20 00 00 01 → 03E8 = 100.0 °C. Addresses are hex, sent as they are. Function codes 03 read, 06 write single / operation command, 16 write multiple, 08 echoback — no FC04, no coils. At most 106 registers per read.

No Decimal Point on the Wire

Values are integers “ignoring the decimal point position”: 150.0 °C reads as 1500. How many digits are after the point depends on the input type and setting, and the controller says it: Decimal Point Monitor at 0x0420 / 0x2410 (0–3). Divide by 10 to that power. Negative values are two's complement.

Key Registers

4-byte2-byteValueUnit
0x00000x2000Process value÷ 10dp
0x00020x2001Status (2-byte: low 16 bits)bits
0x00040x2002Internal set point÷ 10dp
0x00060x2003Heater current 10.1 A
0x00080x2004MV heating (−5.0…105.0)0.1 %
0x000A0x2005MV cooling0.1 %
0x01060x2103Set point (read / write)÷ 10dp
0x01080x2104Alarm value 1÷ 10dp
0x040C0x2406Status, low 16 bitsbits
0x040E0x2407Status, high 16 bitsbits
0x04200x2410Decimal Point Monitor0–3

Status Bits

BitMeaningBitMeaning
6Input error20Write mode (1 = RAM)
8 / 9Control output heating / cooling23AT running
10 / 11Heater burnout CT1 / CT224RUN/STOP: 1 = STOP
12 / 13 / 14Alarm 1 / 2 / 325Communications writing (1 = on)
2A/D converter error26Auto / manual (1 = manual)

In 2-byte mode bits 16–31 are in the second status register (0x2407): bit 24 is its bit 8.

Writing: Communications Writing First

Every write is refused with exception 04 until Communications Writing is on: FC06 to address 0x0000 with 00 01. Operation commands go to the same address, command code in the high byte: 01 00 RUN / 01 01 STOP, 03 01 start AT, 09 01 manual. Writes go to non-volatile memory, which has a limited number of write cycles — for a set point written often, switch to RAM write mode (04 01).

Common Mistakes

Step-by-Step: Reading an E5CC with ModbusManager

  1. Set PSEL to Modbus, the address and the baud rate, and reset the controller.
  2. In ModbusManager choose RTU, the baud rate, even parity, 1 stop bit, the unit number.
  3. Read FC03 from 0x2000, quantity 6: PV, status, internal SP, heater current, MV.
  4. Read 0x2410 for the decimal point, and divide. Or open the workspace below.

Download a Ready-Made Workspace

Read-only. Nothing is written — no set point, no RUN/STOP; the faceplate's Set button will be refused until you enable Communications Writing. The workspace assumes one decimal (a thermocouple or Pt100 at 0.1 °C); if 0x2410 reads otherwise, change the tags' scale. 9600 8E1, unit 1. Tags, script and dashboard are ModbusManager Pro features; Standard opens the poll windows only.

Omron_E5CC.json

Omron E5CC temperature controller workspace (Modbus RTU). Open via Workspace › Open in ModbusManager Pro, or from the in-app Device library.

Download Workspace

Try it with ModbusManager Pro

PID loop faceplate, alarms on the status bits, historian for PV and MV, and MQTT to Home Assistant. Free 14-day trial. No credit card. Windows 10/11.

Download Pro Trial

A PLC beside the controllers: Siemens S7 over PUT/GET. Scripts that turn status words into flags: Tags and Structured Text. All guides: Modbus device guides.

Frequently Asked Questions

How do I enable Modbus on an Omron E5CC?

In the communications setting level set PSEL from CompoWay/F to Modbus, set the unit number, baud rate and parity, then reset the controller. The factory protocol is CompoWay/F, and new communications settings take effect only after a reset.

Why does the E5CC answer exception 03 at address 0?

Address 0x0000 is the 4-byte map: each value is two registers and must be read from an even address with an even count. Read two registers there, or read one register at 0x2000 in the 2-byte map.

Why does my E5CC temperature read 1500?

The E5CC sends integers without the decimal point. The Decimal Point Monitor (0x2410 in 2-byte mode) says how many digits follow the point: with 1, 1500 is 150.0 °C.

How do I write the set point of an E5CC over Modbus?

First turn on Communications Writing with FC06 to address 0x0000, value 0x0001. Then write the set point at 0x2103 (or 0x0106 in 4-byte mode), without the decimal point. Use RAM write mode for frequent writes.

Which bit shows whether the E5CC is running?

Status bit 24, RUN/STOP — 1 means STOP. In the 2-byte map it is bit 8 of 0x2407.

Sources

Omron, E5□C Digital Temperature Controllers Communications Manual, Cat. No. H175-E1-17 (September 2022), files.omron.eu. Tested against a simulator built from this manual, not against a physical controller.

// beyond the controller

The controllers plus the rest of the line

ModbusManager Pro reads a row of temperature controllers next to meters, drives and PLCs, and republishes the values as one Modbus TCP map or as MQTT topics with Home Assistant discovery.

Modbus gateway software →