Omron's E5CC and E5EC (the E5□C family) temperature controllers have RS-485 and speak Modbus RTU — but not out of the box. They ship set to Omron's own CompoWay/F protocol, they hold every value in two address maps at once, and they send integers with the decimal point left out. This guide covers the switch, the registers a dashboard needs, and how to read the status bits, including the one that says 1 when the controller is stopped.
In the communications setting level (hold the O key 3 s for the initial setting level, then press it under 1 s), set:
| Parameter | Factory | For Modbus |
|---|---|---|
| PSEL | CompoWay/F (cwf) | Modbus (mod) |
| U-NO | 1 | slave address 1–99 |
| BPS | 9.6 | 9600 / 19200 / 38400 / 57600 |
| PRTY | even | even or odd with 1 stop bit, or none with 2 stop bits (8 data bits) |
| SDWT | 20 ms | send data wait time |
Then reset the controller — Omron's manual: new communications settings are enabled by resetting. Until then it still answers in CompoWay/F and a Modbus master sees nothing.
Omron's own example: PV in 4-byte mode 01 03 00 00 00 02, in 2-byte mode 01 03 20 00 00 01 → 03E8 = 100.0 °C. Addresses are hex, sent as they are. Function codes 03 read, 06 write single / operation command, 16 write multiple, 08 echoback — no FC04, no coils. At most 106 registers per read.
Values are integers “ignoring the decimal point position”: 150.0 °C reads as 1500. How many digits are after the point depends on the input type and setting, and the controller says it: Decimal Point Monitor at 0x0420 / 0x2410 (0–3). Divide by 10 to that power. Negative values are two's complement.
| 4-byte | 2-byte | Value | Unit |
|---|---|---|---|
| 0x0000 | 0x2000 | Process value | ÷ 10dp |
| 0x0002 | 0x2001 | Status (2-byte: low 16 bits) | bits |
| 0x0004 | 0x2002 | Internal set point | ÷ 10dp |
| 0x0006 | 0x2003 | Heater current 1 | 0.1 A |
| 0x0008 | 0x2004 | MV heating (−5.0…105.0) | 0.1 % |
| 0x000A | 0x2005 | MV cooling | 0.1 % |
| 0x0106 | 0x2103 | Set point (read / write) | ÷ 10dp |
| 0x0108 | 0x2104 | Alarm value 1 | ÷ 10dp |
| 0x040C | 0x2406 | Status, low 16 bits | bits |
| 0x040E | 0x2407 | Status, high 16 bits | bits |
| 0x0420 | 0x2410 | Decimal Point Monitor | 0–3 |
| Bit | Meaning | Bit | Meaning |
|---|---|---|---|
| 6 | Input error | 20 | Write mode (1 = RAM) |
| 8 / 9 | Control output heating / cooling | 23 | AT running |
| 10 / 11 | Heater burnout CT1 / CT2 | 24 | RUN/STOP: 1 = STOP |
| 12 / 13 / 14 | Alarm 1 / 2 / 3 | 25 | Communications writing (1 = on) |
| 2 | A/D converter error | 26 | Auto / manual (1 = manual) |
In 2-byte mode bits 16–31 are in the second status register (0x2407): bit 24 is its bit 8.
Every write is refused with exception 04 until Communications Writing is on: FC06 to address 0x0000 with 00 01. Operation commands go to the same address, command code in the high byte: 01 00 RUN / 01 01 STOP, 03 01 start AT, 09 01 manual. Writes go to non-volatile memory, which has a limited number of write cycles — for a set point written often, switch to RAM write mode (04 01).
Omron E5CC temperature controller workspace (Modbus RTU). Open via Workspace › Open in ModbusManager Pro, or from the in-app Device library.
PID loop faceplate, alarms on the status bits, historian for PV and MV, and MQTT to Home Assistant. Free 14-day trial. No credit card. Windows 10/11.
A PLC beside the controllers: Siemens S7 over PUT/GET. Scripts that turn status words into flags: Tags and Structured Text. All guides: Modbus device guides.
In the communications setting level set PSEL from CompoWay/F to Modbus, set the unit number, baud rate and parity, then reset the controller. The factory protocol is CompoWay/F, and new communications settings take effect only after a reset.
Address 0x0000 is the 4-byte map: each value is two registers and must be read from an even address with an even count. Read two registers there, or read one register at 0x2000 in the 2-byte map.
The E5CC sends integers without the decimal point. The Decimal Point Monitor (0x2410 in 2-byte mode) says how many digits follow the point: with 1, 1500 is 150.0 °C.
First turn on Communications Writing with FC06 to address 0x0000, value 0x0001. Then write the set point at 0x2103 (or 0x0106 in 4-byte mode), without the decimal point. Use RAM write mode for frequent writes.
Status bit 24, RUN/STOP — 1 means STOP. In the 2-byte map it is bit 8 of 0x2407.
Omron, E5□C Digital Temperature Controllers Communications Manual, Cat. No. H175-E1-17 (September 2022), files.omron.eu. Tested against a simulator built from this manual, not against a physical controller.
ModbusManager Pro reads a row of temperature controllers next to meters, drives and PLCs, and republishes the values as one Modbus TCP map or as MQTT topics with Home Assistant discovery.
Modbus gateway software →We use Google Analytics cookies to see how the site is used. You can accept or decline — declining keeps analytics off. See our Privacy Policy.