Janitza's UMG power analysers hold hundreds of Modbus values, but the ones nearly everybody needs sit in one block: the "frequently required measured values" from address 19000, all Float32. Janitza also lets you choose the byte order by address — the same value read 32768 higher comes back little-endian. This page covers the block, the settings and the traps from Janitza's own address list for the UMG 96-PA.
| Setting | Range | Default |
|---|---|---|
| Device address | 1–250 | 1 |
| Baud rate | Auto, 9600–115200 | Auto |
| Data frame | 1 stop no parity, even, odd, 2 stop no parity | 8N1 |
With baud rate on Auto the meter detects the master's speed from the traffic — convenient, but on a quiet or mixed line set a fixed rate. Note the address range runs to 250, beyond the 247 most masters accept. Function codes: 03 and 04 read, 06 and 16 write, 23 read/write, 02 digital inputs, 08 diagnostics.
All Float32 (two registers). The address list gives plain addresses — no 4xxxx notation and no offset mentioned — so request 19000. If the first value comes out as half a float, your master counts from 1: enter 19001.
| Address | Value | Unit |
|---|---|---|
| 19000 / 19002 / 19004 | Voltage L1-N / L2-N / L3-N | V |
| 19006 / 19008 / 19010 | Voltage L1-L2 / L2-L3 / L3-L1 | V |
| 19012 / 19014 / 19016 | Current L1 / L2 / L3 | A |
| 19018 | Vector sum IN = I1 + I2 + I3 | A |
| 19020 / 19022 / 19024 | Real power L1 / L2 / L3 | W |
| 19026 | Real power sum Psum3 | W |
| 19034 / 19042 | Apparent Ssum3 / reactive Qsum3 | VA / var |
| 19044 / 19046 / 19048 | cos φ (fundamental) L1 / L2 / L3 | — |
| 19050 | Frequency | Hz |
| 19052 | Rotation field: 1 right, 0 none, −1 left | — |
| 19054–19060 | Real energy L1, L2, L3, L1..L3 | Wh |
| 19068 | Real energy consumed, rate 1 | Wh |
| 19076 | Real energy delivered L1..L3 | Wh |
| 19084 / 19092 | Apparent / reactive energy L1..L3 | VAh / varh |
| 19110–19114 | THD voltage L1-N, L2-N, L3-N | % |
| 19116–19120 | THD current L1, L2, L3 | % |
Powers are in watts and energies in watt-hours — a 400 A incomer reads 120 000, not 120. The block has cos φ per phase but no total; divide Psum3 by Ssum3 for that. The same quantities also exist from address 1000 in a different order; use one block, not a mix. Values are refreshed every 200 ms.
Everything in the address list is big-endian at the listed address. Janitza serves the same data little-endian at the address plus 32768: voltage L1-N at 19000 is also at 51768, low byte first. Use that only if your master cannot swap bytes itself — and never mix the two in one poll.
Janitza UMG 96-PA workspace. Open via Workspace › Open in ModbusManager Pro.
Three-phase meter, historian, energy reports and alarms on THD. Free 14-day trial. No credit card. Windows 10/11.
Other meters: Schneider PM3250, Carlo Gavazzi EM340, Eastron SDM630.
In the "frequently required measured values" block from 19000: voltages 19000–19010, currents 19012–19016, powers 19020–19026, cos phi 19044–19048, frequency 19050 and energies from 19054, all Float32 big-endian.
Add 32768 to the address: Janitza serves the same data little-endian there. Voltage L1-N is 19000 big-endian and 51768 little-endian.
The 19000 block is in base units: power in W and energy in Wh. Divide by 1000 for kW and kWh.
The default is Auto, which detects the master's speed; fixed choices are 9600 to 115200. The default frame is 8 data bits, no parity, 1 stop bit, and the device address 1 (range 1 to 250).
The 19000 block has cos phi per phase only. Divide Psum3 (19026) by Ssum3 (19034) for the total, as the workspace's script does.
Janitza, Modbus-address list and Formulary UMG 96-PA / UMG 96-PA-MID+ (from firmware 3.54), doc. no. 2.061.029.3.e (12/2025), and User manual UMG 96-PA / -MID / -MID+ (firmware 2), both from janitza.com. Other UMG models have their own address lists; check the 19000 block in yours. Tested against a simulator built from these documents, not a physical device.
A UMG on the incomer and cheaper meters on the feeders: ModbusManager Pro reads them all, converts W to kW once and republishes one Modbus TCP map or MQTT topics for the EMS.
Modbus gateway software →We use Google Analytics cookies to see how the site is used. You can accept or decline — declining keeps analytics off. See our Privacy Policy.