Every device. One tool. Pay once. Modbus · BACnet · Siemens S7 · one-time licence · also from us: BACManager ↗

Janitza UMG 96-PA Modbus: the 19000 Block and the +32768 Trick

Janitza's UMG power analysers hold hundreds of Modbus values, but the ones nearly everybody needs sit in one block: the "frequently required measured values" from address 19000, all Float32. Janitza also lets you choose the byte order by address — the same value read 32768 higher comes back little-endian. This page covers the block, the settings and the traps from Janitza's own address list for the UMG 96-PA.

ModbusManager Pro dashboard for a Janitza UMG 96-PA on a 400 A main incomer: three-phase meter with voltages, currents around 180 A, powers around 120 kW total, cos phi per phase and total, apparent and reactive power, neutral current, voltage and current THD, rotation field right, energy counters and a trend of total power and current THD
The free workspace below on a simulated UMG 96-PA — three FC03 reads from 19000, Float32 big-endian.

RS-485 Settings

SettingRangeDefault
Device address1–2501
Baud rateAuto, 9600–115200Auto
Data frame1 stop no parity, even, odd, 2 stop no parity8N1

With baud rate on Auto the meter detects the master's speed from the traffic — convenient, but on a quiet or mixed line set a fixed rate. Note the address range runs to 250, beyond the 247 most masters accept. Function codes: 03 and 04 read, 06 and 16 write, 23 read/write, 02 digital inputs, 08 diagnostics.

The Frequently Required Values from 19000

All Float32 (two registers). The address list gives plain addresses — no 4xxxx notation and no offset mentioned — so request 19000. If the first value comes out as half a float, your master counts from 1: enter 19001.

AddressValueUnit
19000 / 19002 / 19004Voltage L1-N / L2-N / L3-NV
19006 / 19008 / 19010Voltage L1-L2 / L2-L3 / L3-L1V
19012 / 19014 / 19016Current L1 / L2 / L3A
19018Vector sum IN = I1 + I2 + I3A
19020 / 19022 / 19024Real power L1 / L2 / L3W
19026Real power sum Psum3W
19034 / 19042Apparent Ssum3 / reactive Qsum3VA / var
19044 / 19046 / 19048cos φ (fundamental) L1 / L2 / L3—
19050FrequencyHz
19052Rotation field: 1 right, 0 none, −1 left—
19054–19060Real energy L1, L2, L3, L1..L3Wh
19068Real energy consumed, rate 1Wh
19076Real energy delivered L1..L3Wh
19084 / 19092Apparent / reactive energy L1..L3VAh / varh
19110–19114THD voltage L1-N, L2-N, L3-N%
19116–19120THD current L1, L2, L3%

Powers are in watts and energies in watt-hours — a 400 A incomer reads 120 000, not 120. The block has cos φ per phase but no total; divide Psum3 by Ssum3 for that. The same quantities also exist from address 1000 in a different order; use one block, not a mix. Values are refreshed every 200 ms.

Byte Order: Add 32768

Everything in the address list is big-endian at the listed address. Janitza serves the same data little-endian at the address plus 32768: voltage L1-N at 19000 is also at 51768, low byte first. Use that only if your master cannot swap bytes itself — and never mix the two in one poll.

Common Mistakes

Step-by-Step: Reading a UMG 96-PA with ModbusManager

  1. On the meter set the device address and a fixed baud rate; leave 8N1.
  2. In ModbusManager choose RTU with the same settings, or TCP for an Ethernet variant.
  3. Poll FC03 from 19000, quantity 54, displayed as Float32: voltages, currents, powers, cos φ, frequency.
  4. Open the workspace below for everything scaled to kW and kWh on a dashboard.

Download a Ready-Made Workspace

Read-only. Nothing is written. Unit ID 1. Tags, script and dashboard are ModbusManager Pro features; Standard opens the poll windows only.

Janitza_UMG96PA.json

Janitza UMG 96-PA workspace. Open via Workspace › Open in ModbusManager Pro.

Download Workspace

Try it with ModbusManager Pro

Three-phase meter, historian, energy reports and alarms on THD. Free 14-day trial. No credit card. Windows 10/11.

Download Pro Trial

Other meters: Schneider PM3250, Carlo Gavazzi EM340, Eastron SDM630.

Frequently Asked Questions

Where are the main values in a Janitza UMG 96-PA?

In the "frequently required measured values" block from 19000: voltages 19000–19010, currents 19012–19016, powers 19020–19026, cos phi 19044–19048, frequency 19050 and energies from 19054, all Float32 big-endian.

How do I read Janitza values in little-endian?

Add 32768 to the address: Janitza serves the same data little-endian there. Voltage L1-N is 19000 big-endian and 51768 little-endian.

Why is the Janitza power value so large?

The 19000 block is in base units: power in W and energy in Wh. Divide by 1000 for kW and kWh.

What baud rate does the UMG 96-PA use?

The default is Auto, which detects the master's speed; fixed choices are 9600 to 115200. The default frame is 8 data bits, no parity, 1 stop bit, and the device address 1 (range 1 to 250).

Does the UMG 96-PA give a total power factor?

The 19000 block has cos phi per phase only. Divide Psum3 (19026) by Ssum3 (19034) for the total, as the workspace's script does.

Sources

Janitza, Modbus-address list and Formulary UMG 96-PA / UMG 96-PA-MID+ (from firmware 3.54), doc. no. 2.061.029.3.e (12/2025), and User manual UMG 96-PA / -MID / -MID+ (firmware 2), both from janitza.com. Other UMG models have their own address lists; check the 19000 block in yours. Tested against a simulator built from these documents, not a physical device.

// incomer and sub-meters

The incomer and every sub-meter in one map

A UMG on the incomer and cheaper meters on the feeders: ModbusManager Pro reads them all, converts W to kW once and republishes one Modbus TCP map or MQTT topics for the EMS.

Modbus gateway software →