Danfoss VLT drives speak Modbus RTU on their built-in RS-485 port, but only once you select it: the same port also runs Danfoss's own FC protocol, every parameter sits at ten times its number, and every value is an integer you have to scale by the parameter's conversion index. This page covers the setup, the control and status words, how to read any parameter and how to scale it — from Danfoss's FC 102 design and programming guides, with the FC 302 checked against its own programming guide.
| Parameter | Set to | Note |
|---|---|---|
| 8-30 Protocol | Modbus RTU | The other choices include Danfoss's FC protocol. The change applies only after a power cycle. |
| 8-31 Address | 1–247 | The range depends on the protocol chosen in 8-30 |
| 8-32 Baud Rate | 2400–115200 | Default depends on 8-30 |
| 8-33 Parity / Stop Bits | Even, 1 stop bit | The Modbus default |
| 8-35 / 8-36 | — | Minimum / maximum response delay |
| 8-03 / 8-04 | Timeout time / function | 8-04 is Off by default: a lost master does not stop the drive |
Terminals 68 (+) and 69 (−) on the control card; switch S801 (BUS TER.) switches on the termination at the end of the line. To run the motor from Modbus, the control word must be accepted: 8-50 to 8-56 decide how its bits combine with the digital inputs, and bit 10 of the control word itself must be 1.
Danfoss maps every parameter into the holding registers: parameter P (group × 100 + index) is register 10 × P. Danfoss's own example reads 3-03 Maximum Reference, "register 03030", at address 0BD5 = 3029: on the wire it is one less, as with any 4xxxx register. So:
| Parameter | Register | Wire | Type | Scale |
|---|---|---|---|---|
| 16-13 Frequency | 16130 | 16129 | Uint16 | ÷ 10 → Hz |
| 16-14 Motor Current | 16140 | 16139 | Int32 | ÷ 100 → A |
| 16-10 Power [kW] | 16100 | 16099 | Int32 | × 10 W (÷ 100 → kW) |
| 16-12 Motor Voltage | 16120 | 16119 | Uint16 | ÷ 10 → V |
| 16-30 DC Link Voltage | 16300 | 16299 | Uint16 | V |
| 16-34 Heatsink Temp. | 16340 | 16339 | Uint8 | °C |
| 16-03 Status Word | 16030 | 16029 | V2 | bits |
| 16-90 / 16-92 Alarm / Warning Word | 16900 / 16920 | 16899 / 16919 | Uint32 | bits |
Conversion index: parameters travel as whole numbers, and each one's index in the programming guide says where the decimal point is: −1 means divide by 10, −2 by 100, +1 multiply by 10. 16-10 is the odd one — index 1 in watts, so the bus value counts in 10 W steps. 32-bit values take two registers, high word first: Danfoss's example returns 0016 E360 = 1 500 000 for 1500 rpm.
| Register | Wire | Content | Direction |
|---|---|---|---|
| 50000 | 49999 | CTW, control word | master → drive |
| 50010 | 50009 | REF, bus reference | master → drive |
| 50200 | 50199 | STW, status word | drive → master |
| 50210 | 50209 | MAV, main actual value | drive → master |
The same words are also coils 1–16 (CTW), 17–32 (REF), 33–48 (STW) and 49–64 (output frequency). REF and MAV are percent: 16384 (0x4000) = 100 %, negative in two's complement. Coil 65 decides whether parameter writes go to RAM only (0) or also to EEPROM (1).
Most bits are "1 = keep running": 02 = 0 is a DC brake, 03 = 0 coasts, 04 = 0 is a quick stop, 05 = 0 freezes the output, 06 = 1 starts and 0 ramps down, 07 resets on a 0→1 edge, 10 = 1 marks the word as valid. A run command therefore sets bits 2–6 and 10: 0x047C; clearing bit 6 (0x043C) ramps to stop. Bits 13/14 select the set-up, 15 reverses, 11/12 drive relays 01 and 04 when 5-40 is set to the control word bits.
| Bit | 1 means | Bit | 1 means |
|---|---|---|---|
| 0 | Control ready | 8 | Speed = reference |
| 1 | Drive ready | 9 | Bus control (0 = local) |
| 2 | Enable (not coasting) | 10 | Frequency limit OK |
| 3 | Trip | 11 | In operation |
| 4 | Error, no trip | 12 | Stopped, auto start |
| 6 | Triplock | 13 / 14 / 15 | Voltage / torque / timer exceeded |
| 7 | Warning |
A drive running at its reference under bus control reads 0x0F07.
Danfoss VLT FC 102 / FC 302 read-only workspace. Open via Workspace › Open in ModbusManager Pro.
Drive faceplate, status bits, historian and alarms. Free 14-day trial. No credit card. Windows 10/11.
Other drives: ABB ACH580, ABB ACS580, and references across brands in the VFD speed reference guide.
Set 8-30 Protocol to Modbus RTU, 8-31 the address, 8-32 the baud rate and 8-33 parity (even, 1 stop bit by default), then power the drive off and on: the protocol change applies only after a power cycle.
Ten times the parameter number: 16-13 Frequency is register 16130, which is address 16129 on the wire. 32-bit parameters use two registers, high word first.
Parameters are transferred as integers. 16-13 has conversion index -1, so 427 means 42.7 Hz. Motor current 16-14 (index -2) is in 0.01 A, power 16-10 in 10 W steps.
Control word 50000, bus reference 50010, status word 50200 and main actual value 50210 (on the wire one less). Reference and actual value are scaled 16384 = 100 %.
The FC 301/FC 302 programming guide has the same 8-30 Modbus RTU option, baud rates and 16-1x readouts with the same data types and conversion indexes. Check parameters that exist only on one drive in its own guide.
Danfoss, VLT HVAC Drive FC 102 Design Guide MG11BC02 (06/2014), chapter 8 "RS-485 Installation and Set-up"; VLT HVAC Drive FC 102 Programming Guide, software 7.61, AU430028034214en (2024.10); VLT AutomationDrive FC 301/FC 302 Programming Guide, software 9.5x, AU275636650261en (2024.09). All public at assets.danfoss.com. The guides do not say what the drive answers for a register between two parameters; the workspace avoids those. Tested against a simulator built from these documents, not a physical drive.
A plant room has several FC 102s on one RS-485 line. ModbusManager Pro polls them all, applies the conversion indexes once and republishes Hz, A and kW as one Modbus TCP map for the BMS or a PLC.
Modbus gateway software →We use Google Analytics cookies to see how the site is used. You can accept or decline — declining keeps analytics off. See our Privacy Policy.