Every device. One tool. Pay once. Modbus · BACnet · Siemens S7 · one-time licence · also from us: BACManager ↗

Danfoss VLT FC 102 / FC 302 Modbus RTU: Registers and Scaling

Danfoss VLT drives speak Modbus RTU on their built-in RS-485 port, but only once you select it: the same port also runs Danfoss's own FC protocol, every parameter sits at ten times its number, and every value is an integer you have to scale by the parameter's conversion index. This page covers the setup, the control and status words, how to read any parameter and how to scale it — from Danfoss's FC 102 design and programming guides, with the FC 302 checked against its own programming guide.

ModbusManager Pro dashboard for a Danfoss VLT FC 102 on a chilled-water pump: drive faceplate running at about 43 Hz, 19 A and 10 kW; FC-profile status word 50200 bit by bit; motor voltage, DC link, main actual value in percent, heatsink temperature, alarm word and a frequency and current trend
The free read-only workspace below on a simulated FC 102 — parameters at 10 × number − 1, scaled by their conversion index.

Setting Up the RS-485 Port

ParameterSet toNote
8-30 ProtocolModbus RTUThe other choices include Danfoss's FC protocol. The change applies only after a power cycle.
8-31 Address1–247The range depends on the protocol chosen in 8-30
8-32 Baud Rate2400–115200Default depends on 8-30
8-33 Parity / Stop BitsEven, 1 stop bitThe Modbus default
8-35 / 8-36—Minimum / maximum response delay
8-03 / 8-04Timeout time / function8-04 is Off by default: a lost master does not stop the drive

Terminals 68 (+) and 69 (−) on the control card; switch S801 (BUS TER.) switches on the termination at the end of the line. To run the motor from Modbus, the control word must be accepted: 8-50 to 8-56 decide how its bits combine with the digital inputs, and bit 10 of the control word itself must be 1.

Register = 10 × Parameter Number

Danfoss maps every parameter into the holding registers: parameter P (group × 100 + index) is register 10 × P. Danfoss's own example reads 3-03 Maximum Reference, "register 03030", at address 0BD5 = 3029: on the wire it is one less, as with any 4xxxx register. So:

ParameterRegisterWireTypeScale
16-13 Frequency1613016129Uint16÷ 10 → Hz
16-14 Motor Current1614016139Int32÷ 100 → A
16-10 Power [kW]1610016099Int32× 10 W (÷ 100 → kW)
16-12 Motor Voltage1612016119Uint16÷ 10 → V
16-30 DC Link Voltage1630016299Uint16V
16-34 Heatsink Temp.1634016339Uint8°C
16-03 Status Word1603016029V2bits
16-90 / 16-92 Alarm / Warning Word16900 / 1692016899 / 16919Uint32bits

Conversion index: parameters travel as whole numbers, and each one's index in the programming guide says where the decimal point is: −1 means divide by 10, −2 by 100, +1 multiply by 10. 16-10 is the odd one — index 1 in watts, so the bus value counts in 10 W steps. 32-bit values take two registers, high word first: Danfoss's example returns 0016 E360 = 1 500 000 for 1500 rpm.

One parameter per request. The registers between two parameters (16131–16139…) are not data. Read each parameter on its own, with 1 register for 16-bit types and 2 for 32-bit. Array parameters use holding register 9 as the index pointer: write the index there first.

Control and Status Words

RegisterWireContentDirection
5000049999CTW, control wordmaster → drive
5001050009REF, bus referencemaster → drive
5020050199STW, status worddrive → master
5021050209MAV, main actual valuedrive → master

The same words are also coils 1–16 (CTW), 17–32 (REF), 33–48 (STW) and 49–64 (output frequency). REF and MAV are percent: 16384 (0x4000) = 100 %, negative in two's complement. Coil 65 decides whether parameter writes go to RAM only (0) or also to EEPROM (1).

Control word, FC profile

Most bits are "1 = keep running": 02 = 0 is a DC brake, 03 = 0 coasts, 04 = 0 is a quick stop, 05 = 0 freezes the output, 06 = 1 starts and 0 ramps down, 07 resets on a 0→1 edge, 10 = 1 marks the word as valid. A run command therefore sets bits 2–6 and 10: 0x047C; clearing bit 6 (0x043C) ramps to stop. Bits 13/14 select the set-up, 15 reverses, 11/12 drive relays 01 and 04 when 5-40 is set to the control word bits.

Status word, FC profile

Bit1 meansBit1 means
0Control ready8Speed = reference
1Drive ready9Bus control (0 = local)
2Enable (not coasting)10Frequency limit OK
3Trip11In operation
4Error, no trip12Stopped, auto start
6Triplock13 / 14 / 15Voltage / torque / timer exceeded
7Warning

A drive running at its reference under bus control reads 0x0F07.

Common Mistakes

Step-by-Step: Reading an FC 102 with ModbusManager

  1. Set 8-30 = Modbus RTU, 8-31 address, 8-32 baud rate, 8-33 even parity; power the drive off and on.
  2. Wire terminals 68 / 69, S801 ON at the end of the line.
  3. In ModbusManager choose RTU with the same baud rate, Even parity, 1 stop bit.
  4. Read FC03 address 50199, quantity 1: the status word. 0x0F07 is a running drive.
  5. Open the workspace below for the scaled parameters on a dashboard.

Download a Ready-Made Workspace

Read-only. No control word, no reference: Start / Stop on the faceplate are disabled. Safe on a drive in service. Unit ID 1. Tags and dashboard are ModbusManager Pro features; Standard opens the poll windows only.

Danfoss_FC102_monitor.json

Danfoss VLT FC 102 / FC 302 read-only workspace. Open via Workspace › Open in ModbusManager Pro.

Download Workspace

Try it with ModbusManager Pro

Drive faceplate, status bits, historian and alarms. Free 14-day trial. No credit card. Windows 10/11.

Download Pro Trial

Other drives: ABB ACH580, ABB ACS580, and references across brands in the VFD speed reference guide.

Frequently Asked Questions

How do I enable Modbus RTU on a Danfoss FC 102?

Set 8-30 Protocol to Modbus RTU, 8-31 the address, 8-32 the baud rate and 8-33 parity (even, 1 stop bit by default), then power the drive off and on: the protocol change applies only after a power cycle.

What is the Modbus register of a Danfoss parameter?

Ten times the parameter number: 16-13 Frequency is register 16130, which is address 16129 on the wire. 32-bit parameters use two registers, high word first.

Why does the Danfoss frequency read 10 times too high?

Parameters are transferred as integers. 16-13 has conversion index -1, so 427 means 42.7 Hz. Motor current 16-14 (index -2) is in 0.01 A, power 16-10 in 10 W steps.

Which registers hold the Danfoss control and status word?

Control word 50000, bus reference 50010, status word 50200 and main actual value 50210 (on the wire one less). Reference and actual value are scaled 16384 = 100 %.

Does the FC 302 use the same Modbus registers?

The FC 301/FC 302 programming guide has the same 8-30 Modbus RTU option, baud rates and 16-1x readouts with the same data types and conversion indexes. Check parameters that exist only on one drive in its own guide.

Sources

Danfoss, VLT HVAC Drive FC 102 Design Guide MG11BC02 (06/2014), chapter 8 "RS-485 Installation and Set-up"; VLT HVAC Drive FC 102 Programming Guide, software 7.61, AU430028034214en (2024.10); VLT AutomationDrive FC 301/FC 302 Programming Guide, software 9.5x, AU275636650261en (2024.09). All public at assets.danfoss.com. The guides do not say what the drive answers for a register between two parameters; the workspace avoids those. Tested against a simulator built from these documents, not a physical drive.

// more than one drive

Pumps and fans in one map

A plant room has several FC 102s on one RS-485 line. ModbusManager Pro polls them all, applies the conversion indexes once and republishes Hz, A and kW as one Modbus TCP map for the BMS or a PLC.

Modbus gateway software →