The DSE7320 MKII is Deep Sea Electronics' auto-mains-failure (AMF) controller: it watches the mains, starts the generator when the mains fails, transfers the load and back again. On RS-485 it speaks Modbus RTU through DSE's GenComm register standard. GenComm is logical once you see it — addresses are pages of 256, values that cannot be read come back as sentinel numbers instead of errors, and the start / stop / auto buttons are written as a key and its complement.
GenComm groups registers in pages of 256: register address = page × 256 + offset, the wire address starting at 0. Control mode is page 3 offset 4 = 772; battery voltage is page 4 offset 5 = 1029; generator L1-N is page 4 offset 8 = 1032. A tool that numbers 4xxxx from 1 needs 41033 for the last one. 32-bit values are most significant word first, always at an even address, and must be read in one request.
| Page / offset | Address | Value | Scale |
|---|---|---|---|
| 3 / 4 | 772 | Control mode: 0 stop, 1 auto, 2 manual, 3 test on load, 4 auto with manual restore, 6 test off load, 7 off | — |
| 3 / 6 | 774 | Flags: 13/16 shutdown alarm, 12/16 electrical trip, 11/16 warning, 14/16 control unit failure | bits |
| 4 / 0–3 | 1024–1027 | Oil pressure, coolant temperature, oil temperature, fuel level | kPa, °C, °C, % |
| 4 / 5, 6, 7 | 1029–1031 | Battery voltage, engine speed, generator frequency | 0.1 V, rpm, 0.1 Hz |
| 4 / 8–13 | 1032–1037 | Generator L1 / L2 / L3-N voltage (U32) | 0.1 V |
| 4 / 20–25 | 1044–1049 | Generator L1 / L2 / L3 current (U32) | 0.1 A |
| 4 / 28–33 | 1052–1057 | Generator L1 / L2 / L3 power (S32) | W |
| 4 / 35, 36–41 | 1059, 1060–1065 | Mains frequency, mains L-N voltages | 0.1 Hz, 0.1 V |
| 6 / 0–1 | 1536–1537 | Generator total power (S32) | W |
| 6 / 21, 22 | 1557, 1558 | Average power factor, % of full power | 0.01, 0.1 % |
| 7 / 6–7, 8–9, 16–17 | 1798, 1800, 1808 | Engine run time, generator kWh, number of starts (U32) | s, 0.1 kWh, — |
| 154 / 1… | 39425… | Named alarms, four 4-bit codes per register | codes |
A value the controller cannot give comes back as data, not as an exception: 0xFFFF (signed 0x7FFF) unimplemented — mains currents without mains CTs, for example — 0xFFFE over range, 0xFFFD under range, 0xFFFC transducer fault, 0xFFFB bad data. 32-bit values use 0xFFFFFFFF / 0x7FFFFFFF. Filter them before a value goes on a trend or into an alarm.
Each register holds four alarms as 4-bit codes, highest nibble first: offset 1 emergency stop, low oil pressure, high coolant temperature, low coolant temperature; offset 2 under speed, over speed, generator under / over frequency; offset 3 generator low / high voltage, battery low / high voltage; and so on. Codes: 0 disabled, 1 not active, 2 warning, 3 shutdown, 4 electrical trip, 5 controlled shutdown, 15 unimplemented. A healthy controller reads 0x1111.
The buttons are written to page 16: the system control key to offset 8 (address 4104) and its ones' complement to offset 9 (4105), in one FC16 write. Keys are 35700 + function: 35700 stop, 35701 auto, 35702 manual, 35703 test on load, 35705 start, 35708 transfer to generator, 35709 transfer to mains, 35734 reset alarms. GenComm's own example: auto = 35701 (0x8B75), complement 29834 (0x748A). FC06 is not supported, and a key without its complement is ignored.
Deep Sea DSE7320 MKII AMF controller workspace (Modbus RTU, GenComm). Open via Workspace › Open in ModbusManager Pro, or from the in-app Device library.
Generator and transfer-switch elements, alarms on GenComm flags, historian for run hours and fuel, and MQTT to Home Assistant. Free 14-day trial. No credit card. Windows 10/11.
The incomer next to the generator: Socomec DIRIS A-40 or Janitza UMG 96-PA. All guides: Modbus device guides.
Register address = page x 256 + offset, starting at 0 on the wire. Control mode is page 3 offset 4 = 772, battery voltage page 4 offset 5 = 1029, generator L1-N voltage page 4 offset 8 = 1032.
8 data bits, no parity, 1 stop bit - the 73xx family uses 1 stop bit where other DSE controllers use 2. The address and baud rate are set in the module configuration and can be read back on page 1.
GenComm returns sentinels instead of exceptions: 0xFFFF (signed 0x7FFF) means the value is not implemented, 0xFFFE over range, 0xFFFD under range, 0xFFFC transducer fault.
Write the system control key to address 4104 and its ones' complement to 4105 in one FC16 message: 35701 auto, 35700 stop, 35705 start. FC06 is not supported.
DSE supplies the full GenComm specification on request from support@deepseaplc.com, quoting the controller's serial number.
Deep Sea Electronics, GenComm standard for use with generating set control equipment (DSE7310 GenComm, 2019), as hosted by a DSE distributor; DSE7310 MKII & DSE7320 MKII installation instructions 053-181. The RS-485 default address is reported by installers, not documented by DSE. Tested against a simulator built from GenComm, not against a physical controller.
ModbusManager Pro reads the genset controller next to the incomer meter, UPS and PLCs, and republishes the values as one Modbus TCP map or as MQTT topics with Home Assistant discovery.
Modbus gateway software →We use Google Analytics cookies to see how the site is used. You can accept or decline — declining keeps analytics off. See our Privacy Policy.