Every device. One tool. Pay once. Modbus · BACnet · Siemens S7 · one-time licence · also from us: BACManager ↗

Deep Sea DSE7320 Modbus (GenComm): Page × 256 + Offset, Sentinels and Control Keys

The DSE7320 MKII is Deep Sea Electronics' auto-mains-failure (AMF) controller: it watches the mains, starts the generator when the mains fails, transfers the load and back again. On RS-485 it speaks Modbus RTU through DSE's GenComm register standard. GenComm is logical once you see it — addresses are pages of 256, values that cannot be read come back as sentinel numbers instead of errors, and the start / stop / auto buttons are written as a key and its complement.

ModbusManager Pro dashboard for a Deep Sea DSE7320 after a mains failure: generator running at 89 kW, transfer switch on the generator side in auto, three-phase currents about 150 A, control mode Auto, no alarm, 1500 rpm, oil 420 kPa, coolant 83 °C, fuel 64 %, battery 27.4 V, 44 % load, mains 0 V, 1873 starts, 6123 run hours, 41841 kWh, and a load trend
The free workspace below on a simulated DSE7320 — the mains has failed, the generator carries the load in auto.
About the source. DSE does not publish GenComm openly: the full register specification is “obtainable from DSE upon request” at support@deepseaplc.com with the controller's serial number. This page is based on a copy of DSE's GenComm standard that a DSE distributor hosts. Ask DSE for the edition that matches your firmware before you rely on a register for control.

Connection

Page × 256 + Offset

GenComm groups registers in pages of 256: register address = page × 256 + offset, the wire address starting at 0. Control mode is page 3 offset 4 = 772; battery voltage is page 4 offset 5 = 1029; generator L1-N is page 4 offset 8 = 1032. A tool that numbers 4xxxx from 1 needs 41033 for the last one. 32-bit values are most significant word first, always at an even address, and must be read in one request.

Key Registers

Page / offsetAddressValueScale
3 / 4772Control mode: 0 stop, 1 auto, 2 manual, 3 test on load, 4 auto with manual restore, 6 test off load, 7 off—
3 / 6774Flags: 13/16 shutdown alarm, 12/16 electrical trip, 11/16 warning, 14/16 control unit failurebits
4 / 0–31024–1027Oil pressure, coolant temperature, oil temperature, fuel levelkPa, °C, °C, %
4 / 5, 6, 71029–1031Battery voltage, engine speed, generator frequency0.1 V, rpm, 0.1 Hz
4 / 8–131032–1037Generator L1 / L2 / L3-N voltage (U32)0.1 V
4 / 20–251044–1049Generator L1 / L2 / L3 current (U32)0.1 A
4 / 28–331052–1057Generator L1 / L2 / L3 power (S32)W
4 / 35, 36–411059, 1060–1065Mains frequency, mains L-N voltages0.1 Hz, 0.1 V
6 / 0–11536–1537Generator total power (S32)W
6 / 21, 221557, 1558Average power factor, % of full power0.01, 0.1 %
7 / 6–7, 8–9, 16–171798, 1800, 1808Engine run time, generator kWh, number of starts (U32)s, 0.1 kWh, —
154 / 1…39425…Named alarms, four 4-bit codes per registercodes

Sentinels Instead of Errors

A value the controller cannot give comes back as data, not as an exception: 0xFFFF (signed 0x7FFF) unimplemented — mains currents without mains CTs, for example — 0xFFFE over range, 0xFFFD under range, 0xFFFC transducer fault, 0xFFFB bad data. 32-bit values use 0xFFFFFFFF / 0x7FFFFFFF. Filter them before a value goes on a trend or into an alarm.

Named Alarms (Page 154)

Each register holds four alarms as 4-bit codes, highest nibble first: offset 1 emergency stop, low oil pressure, high coolant temperature, low coolant temperature; offset 2 under speed, over speed, generator under / over frequency; offset 3 generator low / high voltage, battery low / high voltage; and so on. Codes: 0 disabled, 1 not active, 2 warning, 3 shutdown, 4 electrical trip, 5 controlled shutdown, 15 unimplemented. A healthy controller reads 0x1111.

Control Keys: Key Plus Complement

The buttons are written to page 16: the system control key to offset 8 (address 4104) and its ones' complement to offset 9 (4105), in one FC16 write. Keys are 35700 + function: 35700 stop, 35701 auto, 35702 manual, 35703 test on load, 35705 start, 35708 transfer to generator, 35709 transfer to mains, 35734 reset alarms. GenComm's own example: auto = 35701 (0x8B75), complement 29834 (0x748A). FC06 is not supported, and a key without its complement is ignored.

Common Mistakes

Step-by-Step: Reading a DSE7320 with ModbusManager

  1. Select Modbus RTU on the RS-485 port in the DSE Configuration Suite and note the address and baud rate.
  2. In ModbusManager choose RTU, that baud rate, no parity, 1 stop bit, the address.
  3. Read FC03 from 772, quantity 3: control mode and flags.
  4. Read FC03 from 1024, quantity 42: engine, generator and mains values. Or open the workspace below.

Download a Ready-Made Workspace

Read-only. Nothing is written — no control keys. Address 10, 8N1; set your module's address and baud rate. The page numbers are from DSE's GenComm standard; check the edition for your firmware. Tags, script and dashboard are ModbusManager Pro features; Standard opens the poll windows only.

DeepSea_DSE7320.json

Deep Sea DSE7320 MKII AMF controller workspace (Modbus RTU, GenComm). Open via Workspace › Open in ModbusManager Pro, or from the in-app Device library.

Download Workspace

Try it with ModbusManager Pro

Generator and transfer-switch elements, alarms on GenComm flags, historian for run hours and fuel, and MQTT to Home Assistant. Free 14-day trial. No credit card. Windows 10/11.

Download Pro Trial

The incomer next to the generator: Socomec DIRIS A-40 or Janitza UMG 96-PA. All guides: Modbus device guides.

Frequently Asked Questions

How do I calculate a DSE GenComm Modbus address?

Register address = page x 256 + offset, starting at 0 on the wire. Control mode is page 3 offset 4 = 772, battery voltage page 4 offset 5 = 1029, generator L1-N voltage page 4 offset 8 = 1032.

What serial settings does a DSE7320 use?

8 data bits, no parity, 1 stop bit - the 73xx family uses 1 stop bit where other DSE controllers use 2. The address and baud rate are set in the module configuration and can be read back on page 1.

Why does a DSE register read 65535?

GenComm returns sentinels instead of exceptions: 0xFFFF (signed 0x7FFF) means the value is not implemented, 0xFFFE over range, 0xFFFD under range, 0xFFFC transducer fault.

How do I start or stop a DSE7320 over Modbus?

Write the system control key to address 4104 and its ones' complement to 4105 in one FC16 message: 35701 auto, 35700 stop, 35705 start. FC06 is not supported.

Where can I get the DSE GenComm register list?

DSE supplies the full GenComm specification on request from support@deepseaplc.com, quoting the controller's serial number.

Sources

Deep Sea Electronics, GenComm standard for use with generating set control equipment (DSE7310 GenComm, 2019), as hosted by a DSE distributor; DSE7310 MKII & DSE7320 MKII installation instructions 053-181. The RS-485 default address is reported by installers, not documented by DSE. Tested against a simulator built from GenComm, not against a physical controller.

// beyond the generator

The generator plus the rest of the switchboard

ModbusManager Pro reads the genset controller next to the incomer meter, UPS and PLCs, and republishes the values as one Modbus TCP map or as MQTT topics with Home Assistant discovery.

Modbus gateway software →