Every device. One tool. Pay once. Modbus · BACnet · Siemens S7 · one-time licence · also from us: BACManager ↗

NIBE S-series Modbus TCP: Register IDs, Degree Minutes and the 20-Register Limit

NIBE's S-series heat pumps — S1155, S1255, S1156, S1256 and the SMO S40 controller with an S2125 outdoor unit — have Modbus TCP built in. No MODBUS 40 card (that was the F-series RTU accessory): switch it on in the menu and read the heat pump on port 502. NIBE publishes the register list; this guide covers switching it on, the IDs a monitoring dashboard needs, the 32-bit word order, and the limits that make a too-big read fail.

ModbusManager Pro dashboard for a NIBE S1255 heat pump: heat pump element running at 2.2 kW with supply 35.2 °C and return 29.6 °C, outdoor 2.3 °C, prioritisation Heat, operating mode Auto, degree minutes -62.8, calculated supply 35.5 °C, compressor 63 Hz, room 21.4 °C, hot water 49.3 °C, brine in 4.0 °C and out 1.3 °C, and a temperature trend
The free workspace below on a simulated S1255 — FC04 measurements, FC03 settings, the heat pump element and a trend on a fixed −20…70 °C axis.

Switch On Modbus TCP

On the heat pump open menu 7.5.9 “Modbus TCP/IP” and activate it; the network settings are in menu 5.2. NIBE requires software 2.2.1 or later. The server listens on TCP port 502.

Function Codes, IDs and Word Order

WhatNIBE S-series
MeasurementsFC04 input registers
SettingsFC03 read, FC06 write single, FC16 write multiple
AddressThe ID in NIBE's table goes on the wire as it is. The USB export writes 30002 or 40012 — that is ID + 30001 / 40001.
16-bit valuess16 / u16; temperatures ÷ 10. u8 and s8 values still take a whole register.
32-bit valuesLow word first: NIBE shows holding 11–12 as “register 12 and register 11”. 32-bit values are written with FC16.
LimitsAt most 20 registers per query and 100 registers per second.

The same ID means different things in the two tables: input 11 is brine out BT11, holding 11 is degree minutes. The function code is part of the address.

Key Registers (S1155 / S1255 / S1156 / S1256)

IDFCValueTypeScale
104Outdoor temperature BT1s16÷ 10 °C
5 / 704Supply BT2 / return BT3s16÷ 10 °C
8 / 904Hot water top BT7 / charging BT6s16÷ 10 °C
10 / 1104Brine in BT10 / brine out BT11s16÷ 10 °C
2604Room temperature BT50s16÷ 10 °C
101704Calculated supply temperatures16÷ 10 °C
102804Operating prioritisation: 10 off, 20 hot water, 30 heat, 40 pool, 60 coolingu16—
102904Additional heat stepsu16—
104604Compressor frequencyu16÷ 10 Hz
110004Compressor status: 0 off, 1 onu16—
1102 / 110404Heating medium pump GP1 / brine pump speedu16%
197504Alarm numberu16—
216604Instantaneous used poweru32÷ 10 W
219504Active alarm: 0 / 1u16—
219604Diverter valve QN10: 0 heating, 1 hot wateru16—
1575–158504Energy: hot water, heat, compressoru32÷ 10 kWh
1103Degree minutes (read / write)s32÷ 10
2203Reset alarmu8—
26 / 3003Heating curve / curve offsets8—
5603Hot water demand: 0 small, 1 medium, 2 large, 4 smart controlu8—
23703Operating mode: 0 auto, 1 manual, 2 additional heat onlyu8—

SMO S40 uses the same IDs for BT1, BT7, BT6, BT50 and QN10, plus 39 (external supply BT25) and 88 (return BT71). An S2125 outdoor unit is read through the indoor unit, with separate IDs per slave — slave 1: 1803 compressor Hz ÷ 10, 1805 defrost (0 off, 1 active, 2 passive), 1621 outdoor BT28, 400 alarm number; slave 2 has its own numbers (1789, 1791, 910).

Degree Minutes

Degree minutes (holding 11, s32 ÷ 10) is the heat pump's heat balance: below zero it is behind the heating demand, and the compressor and additional heat start at set thresholds. It is the most useful single value to trend, and it is 32-bit low word first — read 11–12 as one pair. Read high word first, a value of −60.0 turns into a number in the millions.

Common Mistakes

Step-by-Step: Reading an S1255 with ModbusManager

  1. Activate Modbus TCP in menu 7.5.9 and note the heat pump's IP address (menu 5.2).
  2. In ModbusManager choose TCP, that address, port 502, from a PC on the same private network.
  3. Read FC04, address 7, quantity 5: return, hot water top, hot water charging, brine in, brine out — ÷ 10 for °C.
  4. Read FC03, address 11, quantity 2 and tick Swap: degree minutes ÷ 10.
  5. Open the workspace below for the rest.

Download a Ready-Made Workspace

Read-only. Nothing is written — no degree minutes, no operating mode. Set your heat pump's IP address in the connection. The IDs are those of an S1155/S1255; an SMO S40 shares most of them, check the CSV export. Tags and dashboard are ModbusManager Pro features; Standard opens the poll windows only.

NIBE_S1255.json

NIBE S-series heat pump workspace (Modbus TCP). Open via Workspace › Open in ModbusManager Pro, or from the in-app Device library.

Download Workspace

Try it with ModbusManager Pro

Heat pump element, historian for degree minutes, alarms on the alarm register, and MQTT to Home Assistant. Free 14-day trial. No credit card. Windows 10/11.

Download Pro Trial

The energy meter beside a heat pump is often an Eastron SDM230 or SDM72. Heat pump to Home Assistant: the Modbus to MQTT gateway publishes the same tags with discovery.

Frequently Asked Questions

Does a NIBE S1255 need a MODBUS 40 accessory?

No. The S-series has Modbus TCP built in: activate it in menu 7.5.9 and connect to port 502. MODBUS 40 was the RS-485 accessory for the older F-series.

Why does my Modbus read from a NIBE heat pump fail?

NIBE answers at most 20 registers per query and 100 per second, only to clients on private IP ranges, and only for IDs the unit has. Read short runs of existing IDs with FC04 for measurements and FC03 for settings.

Where are degree minutes in the NIBE Modbus map?

Holding register 11 (FC03), signed 32-bit divided by 10, read as the pair 11–12 with the low word first. It can be written, but only with FC16.

Is the NIBE register ID the Modbus address?

Yes, the ID goes on the wire as it is. The CSV export from menu 7.5.9 writes 3xxxx / 4xxxx numbers, which are the ID plus 30001 or 40001.

Which NIBE register shows the compressor running?

Input register 1100: 0 off, 1 on. The compressor frequency is input 1046 divided by 10 (Hz); on an S2125 outdoor unit it is 1803 for slave 1.

Sources

NIBE, Technical information — Modbus S-series, M12676EN, TIF EN 2608 (published 2026-02-18), assetstore.nibe.se. How the IDs map to wire addresses is not stated in the document; it follows the CSV export format and the open-source NIBE library. Tested against a simulator built from this document, not against a physical heat pump.

// beyond the heat pump

The heat pump plus the rest of the house

ModbusManager Pro reads the heat pump next to its energy meter, the PV inverter and the battery, and republishes the values as one Modbus TCP map or as MQTT topics with Home Assistant discovery.

Modbus gateway software →