NIBE's S-series heat pumps — S1155, S1255, S1156, S1256 and the SMO S40 controller with an S2125 outdoor unit — have Modbus TCP built in. No MODBUS 40 card (that was the F-series RTU accessory): switch it on in the menu and read the heat pump on port 502. NIBE publishes the register list; this guide covers switching it on, the IDs a monitoring dashboard needs, the 32-bit word order, and the limits that make a too-big read fail.
On the heat pump open menu 7.5.9 “Modbus TCP/IP” and activate it; the network settings are in menu 5.2. NIBE requires software 2.2.1 or later. The server listens on TCP port 502.
| What | NIBE S-series |
|---|---|
| Measurements | FC04 input registers |
| Settings | FC03 read, FC06 write single, FC16 write multiple |
| Address | The ID in NIBE's table goes on the wire as it is. The USB export writes 30002 or 40012 — that is ID + 30001 / 40001. |
| 16-bit values | s16 / u16; temperatures ÷ 10. u8 and s8 values still take a whole register. |
| 32-bit values | Low word first: NIBE shows holding 11–12 as “register 12 and register 11”. 32-bit values are written with FC16. |
| Limits | At most 20 registers per query and 100 registers per second. |
The same ID means different things in the two tables: input 11 is brine out BT11, holding 11 is degree minutes. The function code is part of the address.
| ID | FC | Value | Type | Scale |
|---|---|---|---|---|
| 1 | 04 | Outdoor temperature BT1 | s16 | ÷ 10 °C |
| 5 / 7 | 04 | Supply BT2 / return BT3 | s16 | ÷ 10 °C |
| 8 / 9 | 04 | Hot water top BT7 / charging BT6 | s16 | ÷ 10 °C |
| 10 / 11 | 04 | Brine in BT10 / brine out BT11 | s16 | ÷ 10 °C |
| 26 | 04 | Room temperature BT50 | s16 | ÷ 10 °C |
| 1017 | 04 | Calculated supply temperature | s16 | ÷ 10 °C |
| 1028 | 04 | Operating prioritisation: 10 off, 20 hot water, 30 heat, 40 pool, 60 cooling | u16 | — |
| 1029 | 04 | Additional heat steps | u16 | — |
| 1046 | 04 | Compressor frequency | u16 | ÷ 10 Hz |
| 1100 | 04 | Compressor status: 0 off, 1 on | u16 | — |
| 1102 / 1104 | 04 | Heating medium pump GP1 / brine pump speed | u16 | % |
| 1975 | 04 | Alarm number | u16 | — |
| 2166 | 04 | Instantaneous used power | u32 | ÷ 10 W |
| 2195 | 04 | Active alarm: 0 / 1 | u16 | — |
| 2196 | 04 | Diverter valve QN10: 0 heating, 1 hot water | u16 | — |
| 1575–1585 | 04 | Energy: hot water, heat, compressor | u32 | ÷ 10 kWh |
| 11 | 03 | Degree minutes (read / write) | s32 | ÷ 10 |
| 22 | 03 | Reset alarm | u8 | — |
| 26 / 30 | 03 | Heating curve / curve offset | s8 | — |
| 56 | 03 | Hot water demand: 0 small, 1 medium, 2 large, 4 smart control | u8 | — |
| 237 | 03 | Operating mode: 0 auto, 1 manual, 2 additional heat only | u8 | — |
SMO S40 uses the same IDs for BT1, BT7, BT6, BT50 and QN10, plus 39 (external supply BT25) and 88 (return BT71). An S2125 outdoor unit is read through the indoor unit, with separate IDs per slave — slave 1: 1803 compressor Hz ÷ 10, 1805 defrost (0 off, 1 active, 2 passive), 1621 outdoor BT28, 400 alarm number; slave 2 has its own numbers (1789, 1791, 910).
Degree minutes (holding 11, s32 ÷ 10) is the heat pump's heat balance: below zero it is behind the heating demand, and the compressor and additional heat start at set thresholds. It is the most useful single value to trend, and it is 32-bit low word first — read 11–12 as one pair. Read high word first, a value of −60.0 turns into a number in the millions.
NIBE S-series heat pump workspace (Modbus TCP). Open via Workspace › Open in ModbusManager Pro, or from the in-app Device library.
Heat pump element, historian for degree minutes, alarms on the alarm register, and MQTT to Home Assistant. Free 14-day trial. No credit card. Windows 10/11.
The energy meter beside a heat pump is often an Eastron SDM230 or SDM72. Heat pump to Home Assistant: the Modbus to MQTT gateway publishes the same tags with discovery.
No. The S-series has Modbus TCP built in: activate it in menu 7.5.9 and connect to port 502. MODBUS 40 was the RS-485 accessory for the older F-series.
NIBE answers at most 20 registers per query and 100 per second, only to clients on private IP ranges, and only for IDs the unit has. Read short runs of existing IDs with FC04 for measurements and FC03 for settings.
Holding register 11 (FC03), signed 32-bit divided by 10, read as the pair 11–12 with the low word first. It can be written, but only with FC16.
Yes, the ID goes on the wire as it is. The CSV export from menu 7.5.9 writes 3xxxx / 4xxxx numbers, which are the ID plus 30001 or 40001.
Input register 1100: 0 off, 1 on. The compressor frequency is input 1046 divided by 10 (Hz); on an S2125 outdoor unit it is 1803 for slave 1.
NIBE, Technical information — Modbus S-series, M12676EN, TIF EN 2608 (published 2026-02-18), assetstore.nibe.se. How the IDs map to wire addresses is not stated in the document; it follows the CSV export format and the open-source NIBE library. Tested against a simulator built from this document, not against a physical heat pump.
ModbusManager Pro reads the heat pump next to its energy meter, the PV inverter and the battery, and republishes the values as one Modbus TCP map or as MQTT topics with Home Assistant discovery.
Modbus gateway software →We use Google Analytics cookies to see how the site is used. You can accept or decline — declining keeps analytics off. See our Privacy Policy.