The meter is on order, the drive is on another site, the PLC program is due Friday. ModbusManager's Slave tab turns your PC into the Modbus device the master expects — over TCP and RTU, with values that move: sine waves, ramps, counters, random noise and a simulated PID process. It is in the same app as the master, so you can read your own simulator and see exactly what goes over the wire.
Windows 10/11 · TCP & RTU · in Standard ($49) and Pro ($119) · one-time license · 14-day trial
A SCADA tag list, an HMI screen or a PLC's Modbus driver can only be tested against a device that answers. A simulator stands in for it:
Under Slave devices, + adds a block: a slave ID (1–247), a register type (holding registers, input registers, coils or discrete inputs), a start address and a quantity (up to 1000). A slave ID can own several blocks, so a meter with registers at 0 and at 3000 is two blocks of the same ID. Overlapping blocks are refused.
Add more slave IDs and the same PC is a whole bus of devices.
Under Server, start Modbus TCP on any port (502 by default) and/or Modbus RTU on a COM port. The RTU line has its own baud rate, data bits, parity and stop bits, independent of the connection the app uses as a master — so one PC can be master on one port and slave on another.
To test RTU on a single PC, a virtual COM port pair (com0com, for example) connects the two: the master on one end, the simulator on the other.
The Link line says whether a master is really there: which address connected over TCP, how many requests came in and how long ago the last one was. On RTU it shows the request rate and the frames with a bad CRC, which point at a wrong baud rate or parity. Refused requests appear in the request log below with the reason.
A screen that shows 0 everywhere looks fine and proves nothing. Type a value into any register, or give it a simulation from the ⚙ button next to it:
| Type | What it does | Good for |
|---|---|---|
| Counter ↑ / ↓ | Steps up or down between Min and Max | Energy and operating-hour counters, roll-over tests |
| Sine wave | Swings between Min and Max with a set period | Voltages, temperatures, anything that should look alive on a trend |
| Ramp | Rises from Min to Max, then starts again | Tank levels, scaling and alarm limits |
| Random | A new value between Min and Max each interval | Noise, deadband and change detection |
| PID loop | A simulated process with setpoint, output, mode and tuning in six registers | PID faceplates and setpoint writes |
| Static value (Pro) | One typed value, written in the chosen data type | A Float32 or 32-bit value without converting it by hand |
Each type writes the register as UInt16, Int16, Int32, UInt32 or Float32; the 32-bit types take two registers and a word order, high word first or low word first — so you can reproduce the exact layout of the device you are waiting for, including the word order your master has to get right.
Keep the simulation interval well below the master's poll interval, and a sine period at least ten times the poll interval. When the two rates are close, the master sees the same value twice and then skips one, and a smooth curve turns into steps that are not in the device.
A PID loop takes six holding registers: +0 process value ×10, +1 setpoint ×10, +2 output 0–1000, +3 mode (1 = auto), +4 P ×10, +5 I in seconds. Write a new setpoint from the master — or from the dashboard's PID faceplate in Pro — and watch the process follow it.
A simulator that answers everything hides the mistakes your master will make on site. This one answers like hardware:
| The master asks for | The simulator |
|---|---|
| An address outside the blocks of that slave ID | Exception 02, illegal data address — the classic off-by-one between 40001 and 0 shows up here, not on site |
| A slave ID that is not simulated, over TCP | Exception 0B, as a gateway answers for a device that does not respond |
| A slave ID that is not simulated, over RTU | No answer at all — on a shared RS-485 line the device with that ID answers, and a second reply would collide with it |
| A frame with a bad CRC, over RTU | Dropped and counted on the Link line, as a real slave drops it |
| A write to a coil or holding register (FC 05, 06, 15, 16) | The value changes and the write appears in the request log |
ModbusManager is a Modbus master too, so the same PC can read the simulated device and show what a SCADA will get. Here a poll window reads the simulated meter over TCP with Float on: voltage, current, frequency and energy decoded from register pairs. If your SCADA shows something else, the difference is in the SCADA's settings — data type, word order or address base.
In Pro the simulated device can feed everything else: tags and Structured Text, a dashboard, the Historian and alarms — a complete project built and tested before the first real device is wired.
With some Modbus tools the master and the slave simulator are two separate programs, each bought on its own. In ModbusManager the slave simulator is part of both editions, next to the master:
| Standard, $49 | Pro, $119 | |
|---|---|---|
| Modbus master: poll windows, write, chart, serial monitor, scans | ✓ | ✓ |
| Slave simulator over TCP and RTU, several slave IDs | ✓ | ✓ |
| Counter, sine, ramp, random, PID process | ✓ | ✓ |
| Static value in a chosen data type | — | ✓ |
| Dashboard, tags, Historian, alarms, gateway against the simulated devices | — | ✓ |
Coming from Modbus Poll? See ModbusManager as a Modbus Poll alternative.
Yes. The Slave tab of ModbusManager turns the PC into a Modbus TCP and/or RTU slave. You define slave IDs and register blocks, give registers moving values, and point your SCADA, HMI or PLC at it. The same app can read it as a master to check what it sends.
Yes. Add blocks for as many slave IDs (1-247) as you need; each ID can have several blocks of holding registers, input registers, coils and discrete inputs. One TCP port answers all of them, and on RTU each ID answers on the shared line like a separate device.
Yes. Start a TCP server on any port, an RTU server on a COM port with its own baud rate, data bits, parity and stop bits, or both. To test on one PC, use a virtual COM port pair (for example com0com): the master on one port, the simulator on the other.
An address outside the blocks of that slave ID gets exception 02, illegal data address, as a real device answers. On TCP a slave ID that is not simulated gets exception 0B. On RTU it gets no answer at all, because on a shared RS-485 line the device with that ID would answer, and frames with a bad CRC are dropped and counted.
Yes. Writes to coils and holding registers (function codes 05, 06, 15 and 16) change the simulated values and appear in the request log. A PID loop register block follows a setpoint the master writes.
Both. ModbusManager Standard ($49) and Pro ($119) include the slave simulator with counters, sine waves, ramps, random values and the PID process. Pro adds a static-value type and the dashboard, tags, Historian, alarms and gateway that can work against the simulated devices.
Download the trial, open the Slave tab, add a device and start the server. Your master has something to talk to in a minute.
We use Google Analytics cookies to see how the site is used. You can accept or decline — declining keeps analytics off. See our Privacy Policy.